
H3DR-H
H3DR-H
101
Time Ranges
Time ranges
Setting
Setting range
Min. power ON time
S-series
Time scale: x 0.1
0.1 to 1.2 s
0.1 s min.
Time scale: x 1
1 to 12 s
L-series
Time scale: x 1
1 to 12 s
0.3 s min.
Time scale: x 10
10 to 120 s
Note:
If the above minimum power ON time is not secured, the H3DR may not operate. Be sure to secure the above minimum power ON time.
Allow at least 3 s for repeat synchronization of time-out operations (see Precautions on page 107).
Ratings
Rated supply voltage (see note)
100/110/120 VAC (50/60 Hz), 200/220/240 VAC (50/60 Hz), 24 VAC/DC (50/60 Hz),
48 VAC/DC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100/110/120 VAC: approx. 0.5 VA
200/220/240 VAC: approx. 0.8 VA
24 VAC/DC:
approx. 0.17 VA (AC), 0.13 W (DC)
48 VAC/DC:
approx. 0.36 VA (AC), 0.34 W (DC)
Control outputs
Contact output: 5 A at 250 VAC, resistive load (cos
%
= 1)
Note:
A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
Characteristics
Accuracy of operating time
!
1% FS max. (1% FS
!
10 ms max. in ranges of 1.2 s)
Setting error
!
10% FS
!
0.05 s max.
Influence of voltage
!
0.5% FS max. (
!
0.5% FS
!
10 ms in ranges of 1.2 s)
Influence of temperature
!
2% FS max. (
!
2% FS
!
10 ms in ranges of 1.2 s)
Insulation resistance
100 M
$
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed
non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand voltage
3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC
1 kV for 24 VAC/DC, 48 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
for 100 to 120 VAC, 200 to 240 VAC
1.5 kV for 24 VAC/DC, 48 VAC/DC
Noise immunity
!
1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width:
100 ns/1
&
s, 1-ns rise)
Static immunity
Malfunction: 4 kV
Destruction: 8 kV
Vibration resistance
Destruction:10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in three directions
Shock resistance
Destruction: 980 m/s
2
(100G) each in three directions
Malfunction: 98 m/s
2
(10G) each in three directions
Ambient temperature
Operating:--10
"
C to 55
"
C (with no icing)
Storage:
--25
"
C to 65
"
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical:10 million operations min. (under no load at 1,200 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
EMC
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
IEC801-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance:
ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC801-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Enclosure ratings
IEC: IP40
Weight
Approx. 135 g