Specifications
Time Ranges
Time unit
0.05 s
0.1 s
0.25 s
0.5 s
Setting
5
0.5 to 5 s
10
1 to 10 s
50
5 to 50 s
100
10 to 100 s
Ratings
Rated supply voltage
100/110/120 or 200/220/240 VAC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
AC: approx. 10 VA/2 W
Control outputs
5 A at 250 VAC, resistive load (cos
%
= 1)
Minimum permissible load (ref. value): 100 mA at 5 VDC
Characteristics
Accuracy of operating time
!
0.3%
Setting error
!
5%
Star-delta transfer time
!
25% + 5 ms
Reset time
0.5 s max.
Influence of voltage
!
0.5%
Influence of temperature
!
2% max.
Insulation resistance
100 M
$
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts and
between contact and control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction: 1,000 m/s
2
(approx. 100G)
Malfunction: 300 m/s
2
(approx. 30G)
Ambient temperature
Operating: --10
"
C to 55
"
C
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
See “Engineering Data.”
Approved standards
UL (File No. E41515), CSA (File No. LR22310)
Weight
H3BG-8, H3BG-8H: approx. 100 g; H3BG-F, H3BG-FH: approx. 170 g
Engineering Data
S
w
it
c
h
in
g
operat
ions
(x
10
)
3
Load current (A)