H5CL
H5CL
152
Specifications
Item
H5CL-A
j
(AC models)
H5CL-AD
j
(DC models)
Classification
Digital timer
Mounting
DIN track, surface, and flush mounting
Flush mounting
External connections
Socket
Screw terminals
Enclosure ratings
Panel surface: IEC IP66 and NEMA Type 4 (indoors) when Y92S-29 rubber packing is used.
EMC
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
IEC801-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC801-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards
UL 508, CSA C22.2 No.14
Conforms to EN50081-2, prEN50082-2
Digits
4 digits (zero suppress method)
Max. time settings
9.999 s (0.001-s unit), 99.99 s (0.01-s unit), 999.9 s (0.1-s unit), 9999 s (1-s unit),
99 min 59 s (1-s unit), 999.9 min (0.1-min unit), 99 h 59 min (1-min unit), 999.9 h (0.1-h unit)
Display modes
Up (increment) and Down (decrement) (selectable)
Input signals
Start, gate, reset, and key protection
Input method
No-voltage input: via NPN transistor or switching of contact
Operating modes
A (signal ON-delay), F (accumulative operation) (selectable)
Reset system
Power reset (A (signal ON-delay) mode only), external, manual resets
Sensor waiting time
216 ms typ., 250 ms max. (Control output is turned OFF and no input is accepted during
sensor waiting time.)
External power supply
50 mA at 12 VDC (
!
10%)
---
Display
7-segment LEDs (12 mm high, red LEDs for the present value, and 8 mm high, green LEDs for
the set value)
Memory backup
EEP-ROM (overwritten 200,000 times min.), which can store data for 20 years min.
Case
Light gray (Munsell 5Y7/1)
Ratings
Item
H5CL-A
j
(AC models)
H5CL-AD
j
(DC models)
Rated supply voltage
100 to 240 VAC, 50/60 Hz
12 to 24 VDC (permissible ripple: 20% (p-p) max.)
Operating voltage range
85 to 264 VAC, 50/60 Hz
10.8 to 26.4 VDC
Current consumption
Approx. 10 VA
Approx. 3 W
Start, reset, gate inputs
Min. pulse width: 1 ms/20 ms (selectable, same for all three inputs)
Key protection input
Response time: 1 s max.
Power reset
Min. power opening time: 0.5 s (excluding F (accumulative operation) mode)
Control output
Contact output:
SPDT, 3 A at 250 VAC, resistive load (cos
%
=1) (G6B-2114P-US-U used)
Min. applicable load: 10 mA at 5/24 VDC (P level, for reference value)
Transistor output: NPN open collector, 100 mA max. at 30 VDC max.,
residual voltage 1.5 VDC max.