![Omron E5CC-T Скачать руководство пользователя страница 99](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604099.webp)
5 - 5
5 Communications Data for Modbus
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5
-1 V
ariab
le A
re
a (Setting
Rang
e) List
5
074E
2727
HS Alarm 2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0754
272A
Wait Band
H'00000000 (0): OFF
H'00000001 to H'0000270F
(0.1 to 999.9 for Temperature input)
(0.01 to 99.99 for Analog input)
075A
272D
Fixed SP
SP lower limit to SP upper limit
075C
272E
Standby Time
H'00000000 to H'00009959 (hours, minutes)
H'00000000 to H'00009923 (days, hours)
075E
272F
Program SP Shift Value
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0800
2800
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
Advanced
function
setting
0808
2804
Moving Average Count
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
0810
2808
Extraction of Square Root
Low-cut Point
H'00000000 to H'000003E8 (0.0 to 100.0)
Adjustment
1800
3800
Program Selection
H'00000000 to H'00000007 (0 to 7)
Program
1802
3801
Number of Segments
Used
*1
H'00000001 to H'00000020 (32)
1804
3802
Segment Selection
*1
H'00000000 to H'0000001F (31)
1806
3803
Segment Format
*2
H'00000000 (0): Ramp
H'00000001 (1): Soak
H'00000002 (2): Step
1808
3804
Segment SP
*2
SP Lower Limit to SP Upper Limit
180A
3805
Segment Slope
*2
H'00000000 to H'0000270F (0 to 9999)
180C
3806
Segment Time
*2
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
180E
3807
PID Set No.
*1
H'00000000 to H'00000008 (0 to 8), (0): Automatic selection
1810
3808
Alarm Value 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1812
3809
Alarm Value Upper Limit 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1814
380A
Alarm Value Lower Limit 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1816
380B
Alarm Value 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1818
380C
Alarm Value Upper Limit 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
181A
380D
Alarm Value Lower Limit 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
181C
380E
Alarm Value 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
181E
380F
Alarm Value Upper Limit 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1820
3810
Alarm Value Lower Limit 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1822
3811
Alarm Value 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1824
3812
Alarm Value Upper Limit 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1826
3813
Alarm Value Lower Limit 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
1828
3814
Program Repetitions
*1
H'00000000 to H'0000270F (0 to 9999)
182A
3815
Program Link Destination
No.
*1
H'FFFFFFFF (
−
1): No link
H'00000000 to H'00000007 (0 to 7)
*1
The set values for the program specified in the Program Selection parameter are accessed for the following
parameters: No. of Segments Used, Segment Selection, PID Set No., Alarm Values 1 to 4, Alarm Upper Limits 1 to 4,
Alarm Lower Limits 1 to 4, Program Repetitions, Program Link Destination No., Time Signal 1 and 2 Set Segments,
Time Signal 1 and 2 ON Times, and Time Signal 1 and 2 OFF Times. Check the set value of the Program Selection
parameter before accessing these parameters.
*2
The set values for the program specified in the Program Selection parameter and the section specified in the Segment
Selection parameter are accessed for the following parameters: Segment Type, Segment SP, Segment Slope, and
Segment Time. Check the set value of the Program Selection and Segment Selection parameters before accessing
these parameters.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 176: ...7 Component Communications 7 8 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 181: ...Index 1 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186 I Index...
Страница 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 185: ......