1 Communications Methods
1 - 4
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
The E5
@
C-T's communications specifications are set in the communications setting level. These
parameters are set on the E5
@
C-T's front panel. The following table shows the communications param-
eters and their setting ranges.
Highlighted values indicate default settings.
*
When the Protocol Setting parameter is set to Modbus, the communications data length must be 8 bits, and the
communications stop bits must be 1 bit by setting the communications parity to Even/Odd or it must be 2 bits
by setting the parity to None. These two parameters are not displayed on the Controller's display.
Before you carry out communications with the E5
@
C-T, set up the communications unit number, baud
rate, and other parameters by carrying out the following procedure. For details on operations other than
communications parameter setup, refer to the
E5
@
C-T Digital Temperature Controllers User's Manual
(Cat. No. H185).
(1) Press the
O
Key for at least three seconds to move from the "operation level" to the
"initial setting level."
(2) Press the
O
Key for less than one second to move from the "initial setting level" to
the "communications setting level."
(3) Select the parameters as shown below by pressing the
M
Key.
(4) Press the
D
or
U
Key to change the parameter set values.
*
Displayed only when the Protocol Setting parameter is set to CompoWay/F.
1-1-6
Communications Parameters
Item
Code
Settings
Set Values
Communications protocol setting
psel
CompoWay/F /Modbus
cwf
/
mod
Communications unit No.
u-no
0 to 99
0, 1 to 99
Communications baud rate
bps
9.6/19.2/38. 4/57.6 (kbit/s)
9.6/19.2 /38.4/57.6 (kbit/s)
Communications data length *
len
7/8 (bit)
7/8 (bit)
Communications stop bits *
sbit
1/2
1/2
Communications parity
prty
None, Even, Odd
none
/
eVen
/
odd
Send data wait time
sdwt
0 to 99
0 to 99 ms, default time: 20 ms
1-1-7
Communications Parameter Setup
M
M
M
M
M
M
M
bps
9.6
len
7
sbit
2
prty
even
sdwt
20
psel
cwf
u-no
1
Protocol Setting
Comm
u
nications Unit
N
o.
Comm
u
nications
Ba
u
d Rate
Comm
u
nications Data
Length *
Comm
u
nications Stop
Bits *
Comm
u
nications
Parity
Send Data
W
ait Time
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 176: ...7 Component Communications 7 8 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 181: ...Index 1 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186 I Index...
Страница 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 185: ......