![Omron E5CC-T Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604073.webp)
3 - 27
3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1 V
ariab
le A
rea (Setting
Ran
g
e) List
3
Variable
type
Address
Parameter name
Setting (monitor) value
Level
DA (9A)
0000
Program 0 No. of
Segments Used
H'00000001 to H'00000020 (1 to 32)
Program
setting
DA (9A)
0001
Program 0 PID Set
No.
H'00000000 to H'00000008 (0 to 8), (0): Automatic
selection
DA (9A)
0002
Program 0 Alarm
Value 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0003
Program 0 Alarm
Upper Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0004
Program 0 Alarm
Lower Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0005
Program 0 Alarm
Value 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0006
Program 0 Alarm
Upper Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0007
Program 0 Alarm
Lower Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0008
Program 0 Alarm
Value 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
0009
Program 0 Alarm
Upper Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
000A
Program 0 Alarm
Lower Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
000B
Program 0 Alarm
Value 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
000C
Program 0 Alarm
Upper Limit 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
000D
Program 0 Alarm
Lower Limit 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
DA (9A)
000E
Program 0
Program
Repetitions
H'00000000 to H'0000270F (0 to 9999)
DA (9A)
000F
Program 0
Program Link
Destination No.
H'FFFFFFFF (
−
1): No link
H'00000000 to H'00000007 (0 to 7)
DA (9A)
0010
Program 0 Time
Signal 1 Set
Segment
H'00000000 (0) to No. of segments used
−
1
DA (9A)
0011
Program 0 Time
Signal 1 ON Time
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
DA (9A)
0012
Program 0 Time
Signal 1 OFF Time
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
DA (9A)
0013
Program 0 Time
Signal 2 Set
Segment
Hí00000000 (0) to No. of segments used
−
1
DA (9A)
0014
Program 0 Time
Signal 2 ON Time
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 176: ...7 Component Communications 7 8 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 181: ...Index 1 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186 I Index...
Страница 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 185: ......