![Omron E5CC-T Скачать руководство пользователя страница 98](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604098.webp)
5 Communications Data for Modbus
5 - 4
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
0620
2610
SP Mode Setting Monitor
(SP Mode)
H'00000000 (0): Program SP mode
H'00000001 (1): Fixed SP mode
Adjustment
0702
2701
Proportional Band
(Cooling)
*1
H'00000001 to H'0000270F (0.1 to 999.9)
0704
2702
Integral Time (Cooling)
*1
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0706
2703
Derivative Time (Cooling)
*1
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0708
2704
Dead Band
*1
H'FFFFF831 to H'0000270F
(
−
199.9 to 999.9 for temperature input)
(
−
19.99 to 99.99 for analog input)
070A
2705
Manual Reset Value
*1
H'00000000 to H'000003E8 (0.0 to 100.0)
070C
2706
Hysteresis (Heating)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
070E
2707
Hysteresis (Cooling)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
0710
2708
Control Period (Heating)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Initial
setting
0712
2709
Control Period (Cooling)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
0714
270A
Position Proportional Dead
Band
H'00000001 to H'00000064 (0.1 to 10.0)
Adjustment
0716
270B
Open/Close Hysteresis
H'00000001 to H'000000C8 (0.1 to 20.0)
071E
270F
MV at Reset
Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct Setting of
Position Proportional MV parameter set to ON:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Floating position-proportional control or the Direct Setting of
Position Proportional MV parameter set to OFF:
H'FFFFFFFF to H'00000001 (
−
1 to 1)
0722
2711
MV at PV Error
0726
2713
MV Change Rate Limit
H'00000000 to H'000003E8 (0.0 to 100.0)
0730
2718
PV Slope Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
0734
271A
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
0736
271B
Heater Burnout Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0738
271C
Leakage Current 1 Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
073A
271D
HS Alarm 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0746
2723
Process Value Input Shift
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0748
2724
Heater Current 2 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
074A
2725
Heater Burnout Detection 2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
074C
2726
Leakage Current 2 Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
*1
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected
PID set is fixed at PID1.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 176: ...7 Component Communications 7 8 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 181: ...Index 1 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186 I Index...
Страница 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 185: ......