![Omron E5CC-T Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604060.webp)
3 Communications Data for CompoWay/F
3 - 14
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
*1
After communications parameters have been changed, reset the Digital Controller to enable them.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
004C
Protocol Setting
*1
H'00000000 (0): CompoWay/F
H'00000001 (1): Modbus
H'00000002 (2): Component communications
H'00000003 (3): Host Link (FINS)
H'00000004 (4): MC protocol (Format 4)
Communic
ations
setting
C3 (83)
004D
Send Data Wait
Time
*1
H'00000000 to H'00000063 (0 to 99)
C3 (83)
004E
Control Output 1
Assignment
Control output 1 is a relay output or voltage output (for
driving SSR):
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Program end output
H'0000000C (12): Stage output
H'0000000D (13): RUN output
H'0000000E (14): Time signal 1 output
H'0000000F (15): Time signal 2 output
H'00000010 (16): Integrated alarm
H'00000011 (17): Work bit 1
H'00000012 (18): Work bit 2
H'00000013 (19): Work bit 3
H'00000014 (20): Work bit 4
H'00000015 (21): Work bit 5
H'00000016 (22): Work bit 6
H'00000017 (23): Work bit 7
H'00000018 (24): Work bit 8
When control output 1 is a linear current output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
Advanced
function
setting
C3 (83)
004F
Control Output 2
Assignment
Control output 2 is a relay output or voltage output (for
driving SSR):
H'00000000 to H'00000018 (0 to 24)
*
Same as for the Control Output 1 Assignment pa-
rameter.
When control output 2 is a linear current output:
H'00000000 to H'00000002 (0 to 2)
*
Same as for the Control Output 1 Assignment pa-
rameter.
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...