3 Communications Data for CompoWay/F
3 - 10
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
*1
After communications parameters have been changed, reset the Digital Controller to enable them.
Note: The alarm function can also be used in Digital Controllers without auxiliary output terminals. In this case,
confirm alarm occurrences via the status data.
C3 (83)
0010
Communications
Unit No.
*1
H'00000000 to H'00000063 (0 to 99)
Commu
nications
setting
C3 (83)
0011
Communications
Baud Rate
*1
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
C3 (83)
0012
Communications
Data Length
*1
H'00000007 (7): 7
H'00000008 (8): 8
C3 (83)
0013
Communications
Stop Bits
*1
H'00000001 (1): 1
H'00000002 (2): 2
C3 (83)
0014
Communications
Parity
*1
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
Variable
type
Address
Parameter
name
Setting (monitor) value
Level
Содержание E5CC-T
Страница 2: ......
Страница 14: ...Revision History 12 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 176: ...7 Component Communications 7 8 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 181: ...Index 1 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186 I Index...
Страница 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Страница 185: ......