6 - 51
6 Programless Communications
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
6-6 C
onn
ecti
ng to MEL
S
EC
Q-series PLC
s
6
6-6-5 Che
c
king Oper
ation
(2) We will initialize the download areas with the set values from the E5CC-T Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CC-T Controllers.
Double-click
D25
(Request Flag) on the Device Memory Dialog Box. The following dialog
box is displayed. Enter 2 (Initialize Download Areas), click the
Set
Button, and then click the
Close
Button.
(3) We will confirm that the download areas have been initialized.
When initialization is completed, D0 (Response Flag) will change to 1 (Normal End) and
D25 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
area to see if it has been initialized to the values given in the above table.
Confirm this for the No. 1 and No. 2 Controllers as well.