7-7
Section
Analog Outputs
107
Specified Output Values and Analog Output Signals
–10 to 10 V
0 to 10 V
0 to 5 V
1 to 5 V
Analog output signal
Specified output value
(4-digit Hex)
Analog output signal
Specified output value
(4-digit Hex)
Analog output signal
Specified output value
(4-digit Hex)
Analog output signal
Specified output value
(4-digit Hex)
0000
0.0V
–0.5V
10.0V
10.5V
0FA0
1068
FF38
Resolution: 4,000
EC78
–10.0V
–11.0V
+10.0V
+11.0V
1388
157C
EA84
Resolution: 10,000
0000
0.0V
0000
0.0V
–0.25V
5.0V
5.25V
0FA0
1068
FF38
Resolution: 4,000
0000
1.0V
0.8V
5.0V
5.2V
0FA0
1068
FF38
Resolution: 4,000
Applicable Instructions
END Refresh
Use instructions, such as MOV, to store the analog output value in AR 14 and AR
15 and then turn ON the Analog Output Conversion Enable Bit (AR 1600 or
AR 1601).
Immediate Refresh Using Instructions
Outputs can be controlled with SPED and ACC as outlined below.
SPED can be used to vary the output value stepwise.
P: Port specifier
= 001 for analog output 1 and 002 for analog output 2
F: Analog amount
M: Always 000.
(@) SPED
P
000
F
F: Analog Amount
The target analog output value is specified as a 4-digit hexadecimal value.
– 10 to 10 V
EA84 to 157C Hex (–5,500 to 5,500 decimal,
resolution: 11,000)
0 to 10 V, 0 to 5 V, 1 to 5 V
FF38 to 1068 Hex (–200 to 4,200 decimal,
resolution: 4,400)
Содержание CS1 -
Страница 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 20: ......
Страница 40: ......
Страница 60: ......
Страница 146: ......
Страница 166: ......