![Omron CS1 - Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/omron/cs1/cs1_operation-manual_741974076.webp)
5-1
Section
Unit Setup Area
56
5-1
Unit Setup Area
5-1-1 Overview
The Unit Setup Area enables the user to set the functions of the Customizable
Counter Unit through initial software settings. Connect a Programming Device
to the Unit’s peripheral port and make the settings in DM 6600 to DM 6655 of the
Unit’s DM Area.
Note It is not possible to make the settings for the Unit Setup Area in the Customizable
Counter Unit from a CX-Programmer using the PC Setup functions. Make the
settings for in DM 6600 to DM 6655 from the PC Memory Window on the CX-Pro-
grammer.
The Unit Setup Area consists of DM 6600 to DM 6655. These words are divided
according to function and enable timing as shown below.
Address
Function
Enable timing
Operation for setting error
DM 6600 to DM 6604
Overall Unit Settings
Enabled at Startup
SR 24900 turns ON.
DM 6605 to DM 6614
Special I/O
DM 6615 to DM 6629
Overall Unit Settings
Enabled at Startup and
h
i
SR 24901 turns ON.
DM 6630 to DM 6639
Special I/O
when operation starts
DM 6640 to DM 6644
Overall Unit Settings
DM 6645 to DM 6655
Overall Unit Settings
Enabled whenever changed
SR 24902 turns ON.
The default setting (factory setting) for all words in the Unit Setup Area is 0000.
All words in the Unit Setup Area can be reset to 0000 by turning ON SR 25210
(Unit Setup Area Reset Bit) using the Programming Device in PROGRAM mode.
Note
1. When the DM Area is cleared by performing the memory clear operation
from a Programming Console, the Unit Setup Area is also reset.
2. The Unit Setup Area can also be read from the user program. It cannot, how-
ever, be written from the user program. Write to the User Setup Area using a
Programming Device.
3. The Unit Setup Area settings are saved in flash memory. Therefore, even if
the super-capacitor’s saving time elapses, the data will be saved.
Unit Setup Area
Default Settings
Resetting
Содержание CS1 -
Страница 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 20: ......
Страница 40: ......
Страница 60: ......
Страница 146: ......
Страница 166: ......