![Omron CS1 - Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/omron/cs1/cs1_operation-manual_741974069.webp)
4-3
Section
Words Allocated in DM Area
49
4-3
Words Allocated in DM Area
4-3-1 Allocated Words
A total of 100 words are allocated from words in the CPU Unit’s DM Area for Spe-
cial I/O Units (D20000 to D29599) according to the unit number (0 to 95) set for
the Customizable Counter Unit using the rotary switches on the front of the Unit.
•
The following table shows the relationship between the unit number setting
and the CPU Unit’s allocations.
Unit number
Allocated words
0
D20000 to D20099
1
D20100 to D20199
2
D20200 to D20299
3
D20300 to D20399
4
D20400 to D20499
5
D20500 to D20599
6
D20600 to D20699
7
D20700 to D20799
8
D20800 to D20899
9
D20900 to D20999
10
D21000 to D21099
...
...
n
(n
×
100) to (n
×
100) + 99
...
...
95
D29500 to D29599
The allocated words are divided into two areas: The Initial Setting Area (m to
m+9), to which specific functions have been allocated, and general-purpose
words (m+10 to m+99), to which functions have not been allocated.
1, 2, 3...
1. The contents of the Initial Setting Area (m to m+9) are transferred from the
CPU Unit to the Customizable Counter Unit at startup or when the Custo-
mizable Counter Unit is restarted.
2. General-purpose words (m+10 to m+99) can be allocated to user-set words
in the DM, EM, IR, LR, or AR Area in the Customizable Counter Unit. The
contents of general-purpose words are exchanged with the CPU Unit at the
CPU Unit’s I/O refresh (i.e., on the CPU Unit’s timing).
Содержание CS1 -
Страница 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 20: ......
Страница 40: ......
Страница 60: ......
Страница 146: ......
Страница 166: ......