6-4
Section
AR Area
86
Analog Outputs (CS1W-HCA22 Only)
Address
Bits
Function
Details
Controlled
by
Forced
set/reset
AR 14
00 to 15
Analog Output 1
Output Value
If END refresh is set as the analog output
method, the value set here by the user in
4-digit hexadecimal is output from analog
output 1 when analog output is refreshed.
If immediate refresh using instructions is set
as the analog output method, the value
output from analog output port 1 is stored
here in 4-digit hexadecimal for monitoring
when analog output is refreshed.
0 to 10 V, 0 to 5 V, 1 to 5 V:
FF38 to 1068 Hex
–10 to 10 V:
EA84 to 157C Hex
Note 1: The analog output method (END
refresh or immediate refresh using
instructions) is specified in bits 00 to 07 of
DM 6630 in the Unit Setup Area (00 Hex:
END refreshing). The setting applies to both
analog outputs 1 and 2.
Note 2: The output signal range is specified
in DM 6613.
Immediate
refresh
using
instructions:
Unit
END
refresh:
User
Enabled
AR 15
00 to 15
Analog Output 2
Output Value
Same as above (except that analog output 2
is used for analog output and the output
signal range is set in DM 6614).
AR 16
00
Analog Output 1
Conversion Enable
Bit
ON: D/A conversion enabled (an analog
signal is output)
OFF: D/A conversion is not performed
(analog output is held at the value specified
in DM 6613 nd DM 6614)
User
01
Analog Output 2
Conversion Enable
Bit
in DM 6613 and DM 6614)
Note: These bits are cleared when the
Customizable Counter Unit’s operating
mode is switched between RUN or
MONITOR mode and PROGRAM mode.
02 to 15
(Reserved by system.)
Содержание CS1 -
Страница 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 20: ......
Страница 40: ......
Страница 60: ......
Страница 146: ......
Страница 166: ......