9-5
Section
Troubleshooting Flowcharts
141
Yes
No
Check the voltage at
the IR 00002 and IR
00003 terminals.
Check operation by disconnect-
ing wires to 00002 and 00003
terminals and use the Program-
ming Console to turn the inputs
ON and OFF.
No
Replace the Custo-
mizable Counter Unit.
Is the connector
soldering faulty?
Operation OK?
Wire correctly.
Is input wiring
correct?
Rewire the connec-
tor.
Replace connector.
Is connector
making proper con-
tact?
Check input devices
LS1 and LS2.
Return to “start.”
Are the IR 00002
and IR 00003 input indi-
cators operating
normally?
Operation OK?
Replace the Custo-
mizable Counter Unit.
Operation OK?
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Yes
No
Check the voltage at
the IR 00002 and IR
00003 terminals.
A
From
previous
page
Yes
Содержание CS1 -
Страница 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 20: ......
Страница 40: ......
Страница 60: ......
Страница 146: ......
Страница 166: ......