574

Temperature Input Unit Functions

Section 11-6

Adjustment Device 
Connection Diagram

Connect the six-dial resistance box to the input terminals. 

Connect them to the input terminals for the required input from input 0 to 3.

Note

(1) When connecting the six-dial resistance box, use a cable with the same

gauge as the one that will be used for operation.

(2) The personal computer (CX-Integrator) is connected through CompoNet

in the above diagram. If a CS1W-CRM21 or CJ1W-CRM21 Master Unit is
being used, it can be connected through the Master Unit using a periph-
eral bus connection to adjust the Temperature Input Unit.

Input Terminal 
Connections

Checking the Wiring and 
Making Adjustments

Adjusting the Upper and Lower Limit Values

1,2,3...

1.

Set the resistance value on the six-dial resistance box equivalent to the
test value and properly wire the box to the input of the Temperature Input
Unit that is being adjusted.

2.

If the correct resistance cannot be obtained, properly wire the digital mul-
timeter to the six-dial resistance box and measure the resistance.

3.

Connect the CX-Integrator to the CompoNet network and go online.

4.

Upload settings to the CX-Integrator.

5.

Turn ON the power supplies of all Units, including the Temperature Input
Unit to be adjusted. Wait approximately 30 minutes for the Temperature In-
put Unit's internal temperature to stabilize.

6.

Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select 

Parameters - Edit

.

The Configuration Window will be displayed.

7.

Click the tab for the input that will be adjusted and click the 

Adjustment

Button.

CRT1-TS04P

CX-Integrator

Six-dial resistance box

Connect to the input terminals of 
the input being adjusted.

Precision digital multimeter (DMM)

Use to confirm that the six-dial resistance 
box is providing an accurate resistance.

CompoNet

0A

1A

NC

NC

NC

NC

NC

NC

0B

1B

2B

3B

1B

0B

2B

2A

3A

3B

Six-dial resistance box

DMM

Содержание CRT1 - 10-2009

Страница 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...

Страница 2: ......

Страница 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...

Страница 4: ...iv...

Страница 5: ...n some OMRON products often means word and is abbreviated Wd in documentation in this sense The abbreviation PLC means Programmable Controller PC is used however in some Program ming Device displays t...

Страница 6: ...vi...

Страница 7: ...3 Communications Cable 37 2 4 Communications Cable Wiring Examples 42 SECTION 3 Installation and Wiring 47 3 1 Installing Slave Units 48 3 2 Connecting Cables 57 3 3 Preparing Flat Connectors 58 3 4 C...

Страница 8: ...s 363 7 1 Temperature Input Units 364 7 2 Overview of Temperature Input Units 367 7 3 Status Areas 376 7 4 Monitoring Temperature Data 378 7 5 Temperature Input Units 382 SECTION 8 Expansion Units 391...

Страница 9: ...perature Input Unit Functions 540 SECTION 12 Troubleshooting and Maintenance 579 12 1 Indicator Meanings and Troubleshooting 580 12 2 Troubleshooting 581 12 3 Device Maintenance 588 Appendices A Compo...

Страница 10: ...x...

Страница 11: ...ave Units Section 7 describes the Temperature Input Units Section 8 describes the Expansion Units Section 9 describes the Bit Slave Units Section 10 describes the Repeater Unit Section 11 individually...

Страница 12: ...mpoNet Master Unit functions W342 CS1G H CPU H CS1G H CPU EV1 CS1D CPU H CS1D CPU S CS1W SCB V1 CS1W SCU V1 CJ1G H CPU H CJ1G CPU P CJ1G CPU CJ1M CPU CJ1W SCU V1 CP1H X CP1H XA CP1H Y NSJ B G5D NSJ B...

Страница 13: ...AS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBL...

Страница 14: ...that the uses listed may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this manual Nuclear...

Страница 15: ...nfirm actual specifications of purchased products DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are shown PERFORMANCE...

Страница 16: ...xvi...

Страница 17: ...Unit You must read this section and understand the information contained before attempting to set up or operate a CompoNet Network using CompoNet Slave Units or Repeater Units 1 Intended Audience xvi...

Страница 18: ...cient for the systems machines and equipment and be sure to provide the systems machines and equipment with double safety mechanisms This manual provides information for programming and operating the...

Страница 19: ...for such problems external safety measures must be provided to ensure safety in the system WARNING The CPU Unit refreshes I O even when the program is stopped i e even in PROGRAM mode Confirm safety...

Страница 20: ...in malfunction When installing the Units ground to 100 min Wire all connections correctly according to instructions in the manual Always separate Special Flat Cables Standard and Sheathed for differ...

Страница 21: ...ution before actually running it on the Unit Not checking the program may result in unexpected operation Check all wiring and switch settings to be sure they are correct Always turn OFF the power supp...

Страница 22: ...g and other conditions of the equipment or control panel on which the OMRON devices are installed The customer must therefore perform the final check to confirm that devices and the overall machine co...

Страница 23: ...onfiguration of the control panel used other devices connected to the control panel wiring and other conditions You must therefore confirm that the overall machine or equip ment complies with EC Direc...

Страница 24: ...xxiv Conformance to EC Directives 6...

Страница 25: ...els that are available 1 1 Features of CompoNet Slave Units 2 1 1 1 Overview 2 1 1 2 Features of CompoNet Slave Units 2 1 1 3 CompoNet Slave Unit Functions 7 1 2 Slave Unit Models 19 1 2 1 Word Slave...

Страница 26: ...Unit can quickly measure the ON OFF timing of input and output contacts without relying on the ladder program Contact types IN OUT OUT IN IN IN OUT OUT and trigger patterns ON OFF OFF ON ON ON OFF OFF...

Страница 27: ...c tion time for the most recent 4 communication failures within the slave unit This data can be read by using the CX Integrator Input Filters The Slave Units read input values multiple times during th...

Страница 28: ...ting the Number of AD Conversion Points The conversion cycle is 4 ms max when using all 4 analog inputs The AD conversion cycle can be made faster if fewer AD conversion points are used Rate of Change...

Страница 29: ...mperature range can be measured in seconds Explicit messages can be used to see if the measured time has exceeded a monitoring set value The temperature range total time count settings are made by usi...

Страница 30: ...1 V D08S 1 CRT1 D S 1 CRT1 D16SH 1 CRT1B D02S 1 CRT1B D0 SP 1 CRT1 VAD04S CRT1 VDA02S No special tools are required for connections because industry standard e CON connectors are used Electrical cable...

Страница 31: ...evices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfuncti...

Страница 32: ...es Yes Network Power Voltage Monitor Yes Yes I O Power Status Monitor Communications Error History Monitor Yes Yes Input Filter Communications Error Output Yes Yes Preventing Malfunctions Caused by In...

Страница 33: ...ing Units Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Communications Error Output Yes...

Страница 34: ...Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Output Yes Ye...

Страница 35: ...ower Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Communications Error Output Yes Preventing Malfunctions Caused by Inrush Current at I O...

Страница 36: ...s Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Yes Yes Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Out...

Страница 37: ...s Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Yes Yes Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Out...

Страница 38: ...es Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfunctions Caus...

Страница 39: ...Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfunctions Ca...

Страница 40: ...nnected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Communications Error History Monitor Yes Input Filter Communications Error Output Yes Yes Yes Preventing Malfunctions Cau...

Страница 41: ...onitor Communications Error History Monitor Yes Input Filter Communications Error Output Preventing Malfunctions Caused by Inrush Current at I O Startup Power Short circuit Detection Unconnected Line...

Страница 42: ...Naming Units Yes Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes Yes I O Power Status Monitor Communications Error History Monitor Yes Yes Input Filter Yes Yes Yes Yes Yes Yes Yes C...

Страница 43: ...ave Units with 2 tier termi nal blocks and 16 points Bit Slave Units Bit Slave Units are Slave Units that are allocated units of 2 bits in I O memory of the CPU Unit Bit Slave Units Bit Slave Units ar...

Страница 44: ...nal blocks can be attached removed from the Unit Expansion Units can be added 16 inputs PNP CRT1 ID16 1 16 outputs NPN CRT1 OD16 16 outputs PNP CRT1 OD16 1 8 inputs 8 outputs NPN CRT1 MD16 Terminal bl...

Страница 45: ...cted Line Detection 8 inputs NPN CRT1 ID08TAH 8 inputs PNP CRT1 ID08TAH 1 8 outputs NPN CRT1 OD08TAH 8 outputs PNP CRT1 OD08TAH 1 Without Short cir cuit and Discon nected Line Detection 16 inputs NPN...

Страница 46: ...1 MD16S 1 With Short circuit and Dis con nected Line Detec tion 16 inputs NPN CRT1 ID16SH 16 inputs PNP CRT1 ID16SH 1 16 outputs NPN CRT1 OD16SH 16 outputs PNP CRT1 OD16SH 1 8 inputs and 8 outputs NPN...

Страница 47: ...s NPN CRT1 VOD32ML 32 outputs PNP CRT1 VOD32ML 1 16 inputs 16 outputs NPN CRT1 VMD32ML 16 inputs 16 outputs PNP CRT1 VMD32ML 1 Type Appearance I O capacity Model Features Digital I O Slave Units with...

Страница 48: ...4 to 20 mA 2 outputs CRT1 DA02 MS OM RO N AN ALO G TER MIN AL CR T1 AD 04 NS WO RD NO DE AD R X1 X10 0 63 1 2 3 4 5 6 7 8 A D SW ON INPU T RAN GE CH 0 1 INPU T RAN GE CH 2 3 1 2 3 4 5 6 Type Appearan...

Страница 49: ...AD 04 NS WO RD NO DE AD R X1 X10 0 63 1 2 3 4 5 6 7 8 A D SW ON INPU T RAN GE CH 0 1 INPU T RAN GE CH 2 3 1 2 3 4 5 6 Type Appearance I O capacity Model Features Expansion Units with 2 tier Terminal B...

Страница 50: ...4 inputs NPN CRT1B ID04SP 4 inputs PNP CRT1B ID04SP 1 Bit Slave Units with Compact Connec tors 2 inputs NPN CRT1B ID02JS Compact space saving design Internal hook communications con nectors Network p...

Страница 51: ...trunk line adding more nodes increasing the connection distance and changing the type of cable upstream and downstream of the Repeater Unit PO RT2 PO RT2 PORT1 PORT1 PR T PR T NO DE AD R NO DE AD R N...

Страница 52: ...T1 ID16SH 1 Shared with com munications power supply See note CRT1 OD16SH 1 I O power must be supplied externally for connected devices CRT1 MD16SH 1 Shared with com munications power supply only for...

Страница 53: ...e CON Connectors CRT1 VAD04S DIN Track or Mounting Bracket e CON connectors CRT1 VDA02S With MIL Connectors CRT1 VAD04ML MIL connectors CRT1 VDA02ML Temperature Input Units CRT1 TS04T DIN Track Termi...

Страница 54: ...ply to Expansion Slave Unit Digital Input Slave Unit with Expansion Input Unit Example CRT1 ID16 XWT ID16 or XWT ID08 Not required The Expansion Unit uses the same I O power supply as the Digital I O...

Страница 55: ...Elements 32 2 1 2 Segments 34 2 2 Wiring Formations 35 2 3 Communications Cable 37 2 3 1 Cables That Can Be Used 37 2 3 2 Criteria for Selecting Cables 38 2 3 3 Maximum Distance and Number of Connecte...

Страница 56: ...transfers I O data between the PLC and the Slave Units There is only one Master Unit per network The Master Unit must be con nected to the trunk line Multidrop connection on branch line CompoNet Maste...

Страница 57: ...e same physical layer Terminating Resistors With a CompoNet Network the Master Unit is located at one end of the trunk line and a Terminating Resistor is connected to the other end of the trunk line I...

Страница 58: ...k line from the Repeater Unit One power supply cannot be used to supply communications power to more than one line i e to the trunk line and sub trunk line or to two sub trunk lines I O Power Supply A...

Страница 59: ...ranch line Trunk line Segment 1 Master Unit Slave Unit Slave Unit Repeater Unit Repeater Unit Terminating Resistor Terminating Resistor Repeater Unit Terminating Resistor Terminating Resistor Repeater...

Страница 60: ...table shows the conditions and restrictions for each formation Segment range Segment range Master Unit Slave Unit Terminating Resistor Repeater Unit Slave Unit Slave Unit Slave Unit Slave Unit Termin...

Страница 61: ...ly available VCTF cable with four 0 75 mm2 conductors JIS C3306 that meet CompoNet specifications Flat Cable I DCA4 4F10 Standard Flat Cable CompoNet compatible products other than DCA4 4F10 can be us...

Страница 62: ...signal low 0 5 mm2 4 Black BS communications power supply negative side 0 75 mm2 5 max Black BS Red BS White BDH Blue BDL Item Cable type Round cable I Round cable II Flat Cable I Flat Cable II Applic...

Страница 63: ...und cable II Flat Cable I Standard and Flat Cable II Sheathed are treated as different types of cable Restrictions in Distance between Cables of Multiple CompoNet Systems When using more than one Comp...

Страница 64: ...rom the trunk line or sub trunk lines Total branch line length Restrictions on branch line locations Number of Slave Units including Repeater Units 32 32 Master Unit Repeater Unit Trunk line length Br...

Страница 65: ...out branch ing With branch ing Length per trunk line or sub trunk line 100 m 300m 30 m 90m 30 m 90 m Branch line length Not sup ported See note 2 2 5 m 2 5 m Total branch line length Not sup ported Se...

Страница 66: ...Connectors DCN4 TB4 for connecting Units to connect Communications Cables to Master Units Repeater Units and Slave Units To supply the communications power 24 VDC connect the two commu nications powe...

Страница 67: ...nits Connect the communications power supply 24 VDC to the communica tions power supply connector for the Master Unit or Repeater Unit Connect DCN4 TM4 Terminating Resistors and DCN4 TR4 Flat Connec t...

Страница 68: ...Two communications power lines Relay terminal block Open Connector Slave Unit Slave Unit Slave Unit Open Connector 24 VDC communications power supply Communications power supply connector Communicati...

Страница 69: ...d in parallel by using multidrop connections A DCN4 MD4 Multidrop Connector is required for this Only Flat Cable I can be used Communications connector Flat Cable Communications signal lines BS red an...

Страница 70: ...ly Flat Cable I can be used Communications connector Terminating Resistor 121 Master Unit or Repeater Unit Communications power supply 24 VDC Commu nications power Communications power supply connecto...

Страница 71: ...2 Branching Communications Cables 77 3 4 3 Extending Communications Cables 80 3 4 4 Connection Locations for Terminating Resistor 82 3 5 Power Supply Wiring 85 3 5 1 Power Supply Specifications 86 3 5...

Страница 72: ...TA 1 CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA 1 CRT1 ID16TAH 1 CRT1 OD16TAH 1 CRT1 MD16TAH 1 With e CON Connectors CRT1 VID08S 1 DIN Track or Mounting Bracket CRT1 VOD08S...

Страница 73: ...pact Connec tors CRT1B ID02JS 1 M4 screw mounting using CRT1B ATT03 Mounting Bracket CRT1B OD02JS 1 CRT1B ID04JS 1 CRT1B OD04JS 1 CRT1B MD02JS 1 CRT1B MD04JS 1 Repeater Unit CRS1 RPT01 DIN Track or sc...

Страница 74: ...secured 3 1 4 Mounting with a Mounting Bracket Slave Units with e CON connectors CRT1 V D08S 1 CRT1 VAD04S CRT1 VDA02S or MIL connectors CRT1 V D ML 1 CRT1 VAD04ML CRT1 VDA02ML can be panel mounted or...

Страница 75: ...ocedure 1 Attach the Mounting Bracket to the panel surface or wall with two Phillips screws as shown in the following diagram For mounting hole dimensions refer to Dimensions above 18 7 35 mm 13 Mount...

Страница 76: ...ors Mounting Procedure 1 Attach the Mounting Bracket to the panel surface or wall with two Phillips screws as shown in the following diagram For mounting hole dimensions refer to Dimensions above 2 Mo...

Страница 77: ...ontal Mounting to a Wall Units with e CON Connectors CRT1 V D08S 1 CRT1 VAD04S CRT1 VDA02S Units with MIL Connectors CRT1 V D ML 1 CRT1 VAD04ML CRT1 VDA02ML 6 0 45 45 Mounting Bracket mm The Unit show...

Страница 78: ...heck to be sure that the Unit is securely mounted Mounting Bit Slave Units Using Screw Brackets The Bit Slave Units CRT1B ID02S 1 and CRT1B OD02S 1 are installed using the enclosed screw bracket along...

Страница 79: ...1B D02JS 1 or CRT1B D04JS 1 can be mounted using special Mounting Brackets Required Brackets Dimensions CRT1 ATT03 Guides Screw bracket Screw bracket hook Name Model Applicable Slave Unit Mounting Bra...

Страница 80: ...ing holes B Tighten the screws to the following torque Tightening torque 0 9 N m 2 As shown in the following figure press in on the Unit until the internal hooks of the Mounting Bracket make a clickin...

Страница 81: ...in the following table 3 2 1 Round Cable I II Slave Unit Repeater Unit connections Cable branches T branch connections Multidrop connections Open Type Connector Note Bits Slave Units with a Flat Cable...

Страница 82: ...nits are available with a Flat Cable included as a stan dard feature Flat Connector Socket Flat Connector Plug Multidrop Connector Bit Slaves with Compact Connectors Note If a Sheathed Flat Cable II i...

Страница 83: ...ons Cable to a DCN4 MD4 Multidrop Connector when a multidrop con nection is used Flat Connector II Socket DCN5 TR4 Used as a set with the DCN5 BR4 Flat Connector Plug in the following applications Ext...

Страница 84: ...the Cable Stopper Set the Cable Stopper Close the cover secure the hooks and then press down on the cable stopper until it clicks into place Name Appearance Model Application Pliers DWT A01 Crimping...

Страница 85: ...y been set Attaching the Housing Confirm that the cable labels match the cable colors and then temporarily secure the housing to the cover Note The housing cannot be removed from the cover once it has...

Страница 86: ...2 Do not pressure weld the connector cover at the back of the pressure welding block 3 Set the connector in the correct orientation 3 After attaching the cable confirm that it is properly pressure wel...

Страница 87: ...at there are no whiskers on the wires Setting the Cable Stopper when Extending Cable or Connecting a Terminating Resistor A stopper must be set in advance when extending a line or connecting a Ter min...

Страница 88: ...ing to the cover Note The housing cannot be removed from the cover once it has been attached The connector may be damaged if the housing is force fully removed Pressure welding the Connector The conne...

Страница 89: ...sure welded as shown below Processing and Mounting Procedure for DCN4 BR4 Flat Connector Plug Flat Connector Plug Component Names Cutting the Cable Cut the cable perpendicular to the length To prevent...

Страница 90: ...arrows of the con nector cover with the center of the crimping block on the Pliers 2 Squeeze firmly on the Pliers until the lock on the connector clicks into place Note 1 Do not pressure weld the conn...

Страница 91: ...2 3 1 Confirm the colors again and temporarily secure the housing to the cover Pressure welding the Connector Use the DWT A01 Pliers to pressure weld Connector 1 2 3 1 As shown in the following figur...

Страница 92: ...Cut the cable perpendicular to the length To prevent short circuits cut the cable with a sharp blade such as wire cut ters and be sure that there are no whiskers on the wires Setting the Cable Stoppe...

Страница 93: ...te line is in the direction of the side with the open cover with the white line on the cable facing upward T branch Connections Line Extensions and Terminating Resistor Connections 2 Hold the cable so...

Страница 94: ...or on the pressure welding block of the crimping tool As shown below align the center see arrows of the connector cover with the center of the pressure welding block on the Pliers 2 Squeeze firmly on...

Страница 95: ...that the white line is in the direction of the side with the open cover with the white line on the cable facing upward 2 Hold the cable so that it does not move and close the cover Pressure welding t...

Страница 96: ...firmly on the Pliers until the lock on the connector clicks into place 3 After attaching the cable confirm that it is properly pressure welded as shown below Pliers Connector cover Be sure there are...

Страница 97: ...DCN4 MD4 Used to connect Slave Units or Repeater Units to trunk lines sub trunk lines or branch lines by using multidrop connec tions Terminating Resistor DCN4 TM4 This is a Connector type Terminating...

Страница 98: ...ess in on the latches on both sides and pull out the Open Type Connector 2 Open the terminal cover of the Open Type Connector and connect the ca ble wires to BDH communications data high and BDL commu...

Страница 99: ...remove a Connector once it has been attached press in on the latches on both sides of the Connector and pull it out Connecting Flat Cable I for Bit Slave Units with Compact Connectors Connect a DCN4 M...

Страница 100: ...it in until it clicks into place Note To remove a Connector once it has been attached press in on the latches on both sides of the Connector and pull it out Flat Cable II Flat Cable II cannot be used...

Страница 101: ...k first attach the M3 crimp terminals shown below to the wires Using Flat Cable I Attach a DCN4 BR4 Flat Connector Plug to the DCN4 TR4 Flat Connector Socket connected to Communications Cable Installa...

Страница 102: ...cks into place Note To remove a Connector once it has been attached press in firmly on the latches on both sides of the front of the Connector and pull it out Multidrop Connections Using Round Cable I...

Страница 103: ...e communications connector of the Slave Unit or Repeater Unit and then attach two DCN4 BR4 Flat Connec tor Plugs that are already connected to Communications Cables Installation Method 1 2 3 1 Place t...

Страница 104: ...Cables Flat Cable I Attach a DCN4 BR4 Flat Connector Plug to a DCN4 TR4 Flat Connector Socket connected to Communications Cable Installation Method Be sure the surface of the Flat Connector Plug on wh...

Страница 105: ...to Communications Cable Installation Method Orient the Flat Connector Plug so that the white line on the cable is facing downward and press in the Connector until it clicks into place Note To remove a...

Страница 106: ...ow connect the Terminating Resistor at the end of the line so that the length of a is greater than b Round Cable I Connect the cable wires to a DRS1 T Terminating Resistor Master Unit Trunk line Conne...

Страница 107: ...CN4 TR4 Flat Connector Socket connected to the cable Connection Method Push in the Terminating Resistor until it clicks into place Note To remove a Terminating Resistor once it has been connected pres...

Страница 108: ...tor that is connected to the Unit This is only possible when Flat Cable I is used Flat Cable II Attach a DCN5 TM4 Terminating Resistor to the DCN5 TR4 Flat Connector Socket connected to Communications...

Страница 109: ...ors on Repeater Units Communications power supply Used for communications with individual Units and for internal circuit operations of Units I O power supply Used for I O operations for Units with ext...

Страница 110: ...ter Unit or Repeater Unit Communica tions power supply terminals I O power supply terminals 24 VDC I O power supply Round cable II or Flat Cable I II Communications power supply connector on Master Un...

Страница 111: ...urrent number of inputs used sensor current consumption number of sensors used actual load current number of actuators used 2 Use a power supply with sufficient capacity considering the inrush current...

Страница 112: ...e communica tions power supply and the communications power supply connector must be no longer than 3 m Connect an Open Type Connector here Note When using the UL standards please install a unit to re...

Страница 113: ...24 VDC power supply is provided using the following method Units with e CON Connectors CRT1 OD S 1 MD S 1 OD SH 1 and MD SH 1 Connect the 24 VDC power supply line to the V terminal and G terminal of t...

Страница 114: ...nits CRT1 VAD04S are equipped with a sensor power supply connector for supplying of power to the connected sensor Peel back the coating on the included power supply cable and connect the wires to the...

Страница 115: ...an external communications power supply for the Master Unit Not Using a Repeater Unit BS BDH BDL BS V G V G BS BDH BDL BS BS BDH BDL BS BDH BDL BS BS BS BS Termi nating Resistor Communications power s...

Страница 116: ...2 BDL 2 BS 2 BS 2 PORT1 PORT2 BDH BDL BS BS BS BS Master Unit Termi nating Resistor Power supply Slave Unit I O power supply Communications power supply Multi power supply Slave Unit Round cable I Rep...

Страница 117: ...BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 T POR 2 BS 2 BS 2 BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT2 BS 2 BS 2 Termi nating Resis tor Trunk line Slave Units Communications power supply and I O...

Страница 118: ...connected at only one location for the trunk line and one location each for the sub trunk lines Communications power to the trunk line can be supplied only through the communications power supply conn...

Страница 119: ...ommunications errors may occur if this restriction is not observed Trunk line or sub trunk line Sub trunk line Master Unit Repeater Unit Repeater Unit Trunk line or sub trunk line Communications power...

Страница 120: ...G BS BDH BDL BS BS BDH BDL BS BS BDH BDL BS BS BDH BDL BS V G BS BDH BDL BS BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT2 BS 2 BS 2 V G BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT...

Страница 121: ...age drop is expressed by the following formula If the voltage drop is too large and power cannot be supplied to the farthest Slave Unit within the allowable range add a Repeater Unit and supply power...

Страница 122: ...ods Supplying I O Power from One Source When supplying I O power to the entire system from one source the power consumed by each device and all the loads must be considered Select the cables so that...

Страница 123: ...t the overall system from stopping to ensure system safety consider placing power supplies in more than one location and con sider the way Slave Units should be grouped when supplying power Cost Consi...

Страница 124: ...ID16 1 CRT1 OD16 1 CRT1 MD16 1 CRT1 ROS08 CRT1 ROF08 CRT1 ROS16 CRT1 ROF16 With 3 tier Terminal Block CRT1 ID08TA 1 CRT1 OD08TA 1 CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA...

Страница 125: ...ng the other screw the terminal block will warp possibly causing it to crack Analog I O Slave Units With 2 tier Terminal Block CRT1 AD04 Screw terminal block M3 CRT1 DA02 With e CON Connectors CRT1 VA...

Страница 126: ...ROF16 Models with 3 terminal blocks CRT1 ID08TA 1 CRT1 OD08TA CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA 1 CRT1 ID16TAH 1 CRT1 OD16TAH 1 CRT1 MD16TAH 1 Analog I O Slave Uni...

Страница 127: ...connector cover matches the wire color as shown in the following table For Digital I O Slave Unit 37104 2124 000FL Green AWG22 0 3 mm2 to AWG20 0 5 mm2 sheath outer diameter 1 0 to 1 2 mm 37104 2165...

Страница 128: ...in the following diagram 2 Insert the wire all the way to the back of the wire insertion opening Check that the sheath of the line is inserted into the wire insertion opening and that the end of the...

Страница 129: ...nnecting to MIL Connector Terminals Use any of the following methods to connect to a MIL connector Use an OMRON MIL Cable Pressure weld a Flat Cable to a MIL Socket Pressure weld a loose wire cable to...

Страница 130: ...2ML G79 O50 25 D1 50 cm G79 O75 50 D1 75 cm G7TC OC16 OC08 G7OD SOC16 VSOC16 G7OD FOM16 VFOM16 G7OA ZOC16 3 G7OD SOC08 G7OR SOC08 CRT1 VOD32ML 1 G79 O50 25 D1 50 cm G79 O75 50 D1 75 cm G7OD SOC16 1 G7...

Страница 131: ...cut G79 Y100C 1 m G79 Y150C 1 5 m G79 Y200C 2 m G79 Y300C 3 m G79 Y500C 5 m Forked terminals are attached to the loose wires Forked terminal 161071 M2 Nippon Terminal CRT1 V D32ML 40 pins G79 A200C D...

Страница 132: ...Red 18 Red 9 White Black 19 White Black 10 Red 20 Red Pin No Wire color Dots Dot color Pin No Wire color Dots Dot color 1 Light brown Black 21 Light brown Black 2 Red 22 Red 3 Yellow Black 23 Yellow B...

Страница 133: ...release two latches on one side without releasing the latches on the other side 2 Insert the Flat Cable between the separated Socket sides line it up with the contacts align the contact side with the...

Страница 134: ...on individual components refer to the Connectors Group Catalog Cat No G015 Component Wire size AWG24 Wire size AWG28 to AWG26 Socket No polarity guide XG5M 1031 N XG5M 1034 N Uses polarity guide XG5M...

Страница 135: ...must be placed on the cable wires The applicable pin terminals are listed in the following table The pin terminal conductor should be about 8 to 10 mm in length Wiring to the Screw less Clamp Termina...

Страница 136: ...the sealing The cables are held between the sealing section cover and sealing section housing to ensure resistance to splashing For cables with smaller outer diameters the sealing pieces can be used t...

Страница 137: ...the housing as described above Tightening the Cover Finally close the cover and tighten the cover screws The tightening torque is 0 8 to 1 0 N m 3 6 6 Connecting to Compact Connectors The compact conn...

Страница 138: ...te 1 Automated Crimp Tools are also available For details contact the manu facturer 2 For information on the processing procedure refer to the instruction man ual included with the tool or contact the...

Страница 139: ...f Slave Units This section provides the basic specifications of the Slave Units 4 1 Basic Specifications of Slave Units 116 4 1 1 Communications Specifications 116 4 1 2 Performance Specifications 117...

Страница 140: ...Units CompoNet Master Units Connectable Slave Units CompoNet Slave Units Maximum I O capacity Word Slave Units 1 024 inputs and 1 024 outputs 2 048 I O points total Bit Slave Units 256 inputs and 256...

Страница 141: ...to 60 Hz with double amplitude of 0 7 mm 60 to 150 Hz and 50 m s2 in X Y and Z directions for 80 min each Shock resistance 150 m s2 3 times each in 6 directions on 3 axes Dielectric strength 500 VAC b...

Страница 142: ...icipat ing Normal communications are in progress but the node is not yet participating in the network Lit red Fatal communications error The address is set out of range The same address has been set f...

Страница 143: ...ck 177 5 3 13 Sixteen point Output Units 3 tier Terminal Block 183 5 3 14 Eight point Input and Eight point Output Units 3 tier Terminal Block 190 5 4 Units with Connectors 197 5 4 1 Eight point Input...

Страница 144: ...ed to Master Unit The Digital I O Slave Unit has two status areas the Warning Status Area and the Alarm Status Area The status bit detection allocated to the master is OR of all slaves Bit Content Des...

Страница 145: ...e node address set for the Unit Units with 16 I O points 8 inputs and 8 outputs are allocated two words the node address set for the Unit The data is allocated to the lower bytes of the words and the...

Страница 146: ...O Unit Thirty two point Input Unit Thirty two point Output Unit Thirty two point I O Unit Input Area 1 2 3 4 5 6 7 0 Not used Output Area 1 2 3 4 5 6 7 0 Not used Input Area 1 2 3 4 5 6 7 8 9 10 11 12...

Страница 147: ...rea Sixteen point Input Unit Eight point Expansion Output Unit Two node address areas are allocated Node address m in the Input Area and node address m in the Output Area Sixteen point Output Unit Six...

Страница 148: ...utput Unit Eight point Expansion Input Unit Two node address areas are allocated Node address m in the Output Area and node address m in the Input Area Output Area 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Страница 149: ...each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input curren...

Страница 150: ...left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08 NPN Nam...

Страница 151: ...O power supply NC 16 NC 17 NC 18 NC 7 NC 8 NC 9 1 2 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red Black White Blue Black Brown White B...

Страница 152: ...ors prior to the revisions Dimensions Same for CRT1 ID08 and CRT1 ID08 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN...

Страница 153: ...ent 0 5 A output 2 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 m...

Страница 154: ...th the 10s digit set on the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communi...

Страница 155: ...H BDL BS Internal circuits Physical layer DC DC converter not isolated Voltage drop 0 1 G V 24 VDC BS BDH BDL BS Photocoupler Photocoupler Internal circuits DC DC converter not isolated Physical layer...

Страница 156: ...ctive load such as a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an external diode V 10 1 11 3 12 5 13 7 14 NC 15 G 1 0 2 2 3 4 4 6 5 NC 6 24 VDC...

Страница 157: ...nications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector...

Страница 158: ...age 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min...

Страница 159: ...on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID16 NPN CRT1 ID16 1 PNP Name LED status I O status Meaning 0 to 15 Lit yellow Input ON The input is ON Not lit Input OFF...

Страница 160: ...0 2 3 4 4 6 5 8 6 24 VDC I O power supply 11 16 13 17 15 18 10 7 12 8 14 9 1 2 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red Black Whi...

Страница 161: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connecto...

Страница 162: ...and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 16 outputs comm...

Страница 163: ...switches is read when power is turned ON Internal Circuits CRT1 OD16 NPN CRT1 OD16 1 PNP Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The output is ON Not lit Output OFF The output...

Страница 164: ...for absorbing the counterelectromotive force or install an external diode V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC I O power supply Solenoid valve etc 11 16 13 17 15 18 10 7 12 8...

Страница 165: ...unications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connecto...

Страница 166: ...rminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF curre...

Страница 167: ...1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Power supply type Multi power supply Output handling for commu...

Страница 168: ...0 G1 V2 24 VDC G2 DC DC converter not isolated Physical layer Internal circuits Photocoupler Photo coupler Voltage drop Photocoupler Photocoupler 1 DC DC converter not isolated Physical layer Interna...

Страница 169: ...andards for photoelectric and proximity sensors The previous colors are shown in parentheses Solenoid valve etc Solenoid valve etc Brown red Brown white Blue black Blue black 3 wire sensor with NPN ou...

Страница 170: ...cations Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector I...

Страница 171: ...tions on 3 axes Dielectric strength 500 VAC between isolated circuits Insulation resistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to...

Страница 172: ...decimal number with the 10s digit set on the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is...

Страница 173: ...M BS BDH BDL BS DRTA NY5W K 5 VDC Internal circuits Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2...

Страница 174: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Страница 175: ...ide will bend out in the direction of the arrow releasing the hook 3 Using a tool such as a screwdriver press down on the relay socket lever and remove the Relay from the socket 0 1 0 3 0 5 1 3 5 2 3...

Страница 176: ...esistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage t...

Страница 177: ...the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1...

Страница 178: ...C SSR SSR 0 1 COM BS BDH BDL BS Internal circuits Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 CO...

Страница 179: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Страница 180: ...lated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage temperature 25 to 65 C Storage...

Страница 181: ...f the output indicators are given in the following table Setting the Node Address The node address is set as a decimal number with the 10s digit set on the left rotary switch and the 1s digit set on t...

Страница 182: ...oto coupler Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 COM0 OUT6 OUT4 OUT1 OUT3 OUT8 OUT7 OUT5...

Страница 183: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Страница 184: ...ide will bend out in the direction of the arrow releasing the hook 3 Using a tool such as a screwdriver press down on the relay socket lever and remove the Relay from the socket 30 VDC t 40 ms 30 VDC...

Страница 185: ...esistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage t...

Страница 186: ...he left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 f...

Страница 187: ...coupler Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 COM0 OUT6 OUT4 OUT1 OUT3 OUT8 OUT7 OUT5 OUT1...

Страница 188: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Страница 189: ...input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms m...

Страница 190: ...Section 5 3 Component Names and Functions Same for CRT1 ID08TA 1 CRT1 ID08TAH 1 Communications indicators MS and NS Node address switches 10 and 1 from left Communications connector I O terminal bloc...

Страница 191: ...aximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08TA NPN Name LED status I O status Meaning 0 to 7 Lit yellow Input ON The input i...

Страница 192: ...rter not isolated Input circuits BS BDH BDL BS V G Input 0 to 7 V Photocoupler Internal circuits Physical layer DC DC converter not isolated Input circuits V G0 to G7 G Disconnection or short circuit...

Страница 193: ...ensor 2 wire sensor e g limit switch 0 V G V G V G V G 1 7 NC Brown white Black white Brown red Blue black Blue black 3 wire sensor with PNP output photoelectric sensor or proximity sensor 2 wire sens...

Страница 194: ...en changed according to the revised JIS standards for photoelectric and proximity sensors The previous colors are shown in parentheses Brown white Black white Brown red Blue black Blue black 3 wire se...

Страница 195: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 196: ...l and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disco...

Страница 197: ...digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS Node address switches 10 and...

Страница 198: ...ge drop Physical layer DC DC converter not isolated Internal circuits BS BDH BDL BS V 24 VDC G V G Output 0 to 7 Photocoupler Voltage drop Physical layer DC DC converter not isolated Internal circuits...

Страница 199: ...pt for the I O power supply terminals 3 Do not wire NC terminals V G V V G G Output 0 to 7 Photo coupler Voltage drop BS BDH BDL BS Physical layer DC DC converter not isolated Internal circuits Discon...

Страница 200: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 201: ...nput terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max...

Страница 202: ...igit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS Node address switches 10 and 1...

Страница 203: ...cal layer BS BDH BDL BS V1 24 VDC G1 G1 0 to 7 V1 V2 24 VDC G2 G2 8 to 15 V2 Photo coupler Photo coupler Internal circuits DC DC converter not isolated Input circuits Input circuits Physical layer G V...

Страница 204: ...Brown red Blue black Blue black 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 3 wire sensor with NPN output photoelectric sensor or proximity se...

Страница 205: ...white Brown red Blue black Blue black Brown white Black white Brown red Blue black Blue black 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 3 wi...

Страница 206: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 207: ...etween each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per common 8 outputs common Load short circuit detection Supported...

Страница 208: ...Section 5 3 Component Names and Functions Same for CRT1 OD16TA 1 CRT1 OD16TAH 1 Communications indicators MS and NS Node address switches 10 and 1 from left Output indicators 0 to 15 Communications co...

Страница 209: ...e setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD16TA NPN Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The output is ON Not lit Output OFF T...

Страница 210: ...converter not isolated Internal circuits Photocoupler Photocoupler Voltage drop Voltage drop BS BDH BDL BS G1 V1 G1 G2 V2 V2 Output 0 to 7 Output 8 to 15 Photocoupler Photocoupler Physical layer DC D...

Страница 211: ...cuits Voltage drop Voltage drop Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit Solenoid valve etc 3 wire external device with NPN input Through beam...

Страница 212: ...tive force or install an external di ode 4 Do not wire NC terminals Dimensions Same for CRT1 OD16TA 1 CRT1 OD16TAH 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Cable Dimensions when...

Страница 213: ...Screw Terminal Blocks Section 5 3 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 106 37 mm 48 45 5 10 m...

Страница 214: ...8 inputs Internal I O common NPN PNP NPN PNP ON voltage 15 VDC min between each input terminal and the V terminal 15 VDC min between each input terminal and the G terminal 10 5 VDC min between each i...

Страница 215: ...ax 0 5 A DC between each output terminal and the G termi nal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load...

Страница 216: ...ow Input or output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status Meaning 0 to 7 inputs Lit red Short circuit detection The power supply...

Страница 217: ...not isolated Physical layer Internal circuits Photocoupler Photocoupler Voltage drop Input circuits 0 to 7 Internal circuits Photocoupler Voltage drop V G G V G V G BS BDH BDL BS DC DC converter not...

Страница 218: ...ensor 3 wire external device with NPN input Through beam emitter of photoelectric sensor 2 wire sensor e g limit switch 0 V1 G1 V1 G1 V1 G1 V1 G1 1 7 0 V2 G2 V2 G2 V2 G2 V2 G2 1 7 NC NC Brown white Bl...

Страница 219: ...JIS standards for photoelectric and proximity sensors The previous colors are shown in parentheses Solenoid valve etc 3 wire sensor with NPN output photoelectric sensor or proximity sensor 3 wire ext...

Страница 220: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 221: ...he G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max in...

Страница 222: ...he 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and...

Страница 223: ...circuits Input circuits Short protection BS BDH BDL BS Internal circuits DC DC converter not isolated Physical layer Photo coupler Photo coupler V0 NC G IN0 V1 NC G IN1 Short protection Input circuits...

Страница 224: ...t photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Black White Blue Black Brown Red Blue Black V V V V V V V V NC NC NC NC NC NC NC NC IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 G0 G1 G2 G...

Страница 225: ...en a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted mm The numbers inside the parenthese...

Страница 226: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted mm 136 5 37 mm 48 10 mm 1...

Страница 227: ...nal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 8 outputs common Isolation met...

Страница 228: ...the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Output indicators 0 to 7 Communications indicato...

Страница 229: ...BS BDH BDL BS Photo coupler Photo coupler V NC G OUT0 V NC G OUT1 V G DC DC converter not isolated Physical layer Internal circuits Voltage drop V NC G OUT0 V NC G OUT1 V G BS BDH BDL BS Photo coupler...

Страница 230: ...rnal device with NPN input Through beam emitter of photoelectric sensor V V V V V V V V NC NC NC NC NC NC NC NC G G G G G G G G 1 2 3 4 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 G V Blue black B...

Страница 231: ...en a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 23 101 7 90 6 4 5 3 60 66 2 102 96 7...

Страница 232: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted mm 136 5 37 mm 48 10 mm 1...

Страница 233: ...the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 11 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Power supply short circuit detec tion Operates at 50 mA...

Страница 234: ...ting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID16S NPN Name LED status I O status Meaning 0 to 15 Lit yellow Input ON The input is ON Not lit Input OFF The input...

Страница 235: ...C G1 IN1 BS BDH BDL BS Internal circuits DC DC converter not isolated Physical layer Input circuits Input circuits Photo coupler Photo coupler Disconnection or short circuit detection circuit Disconne...

Страница 236: ...NC G11 IN 11 V NC G12 IN 12 V NC G13 IN 13 V NC G14 IN 14 V NC G15 IN 15 3 4 1 2 3 4 G0 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red...

Страница 237: ...ommunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connec...

Страница 238: ...tput terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection detec tion Operates at 3 mA point max Does not...

Страница 239: ...rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and 1 from left Output indicators 0 to...

Страница 240: ...otocoupler Photocoupler V NC G OUT1 V NC G OUT0 V G G V Internal circuits DC DC converter not isolated Physical layer Voltage drop Voltage drop Internal circuits Voltage drop Photocoupler Photocoupler...

Страница 241: ...isolated Physical layer BS BDH BDL BS Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit V NC G OUT1 V V G G NC V G OUT0 Internal circuits Voltage drop P...

Страница 242: ...ither V terminal Connection can be made to either G terminal V NC G OUT 8 NC G OUT 9 NC G OUT 10 NC G OUT 11 NC G OUT 12 NC G OUT 13 NC G OUT 14 NC G OUT 15 1 2 3 4 V V V V V V V V G V NC G OUT 0 NC G...

Страница 243: ...Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Conn...

Страница 244: ...ecification Model CRT1 MD16S CRT1 MD16S 1 CRT1 MD16SH CRT1 MD16SH 1 I O capacity 8 inputs Internal I O common NPN PNP NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10...

Страница 245: ...ter minal and the G terminal 1 2 V max 0 5 A DC between each output ter minal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Suppor...

Страница 246: ...ame LED status I O status Meaning 0 to 7 inputs 0 to 7 outputs Lit yellow Input or output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status...

Страница 247: ...ernal circuits Photo coupler Photocoupler V1 NC G0 IN0 V NC G OUT0 V G G V Physical layer Input circuits Short protection Voltage drop Internal circuits V0 NC G1 IN0 V V G G NC V G OUT0 BS BDH BDL BS...

Страница 248: ...rcuits Voltage drop Internal circuits Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit BS BDH BDL BS DC DC converter not isolated Photo coupler Photoco...

Страница 249: ...proximity sensor 3 wire external device with NPN input Through beam emitter of photoelectric sensor 2 wire sensor e g limit switch Brown Red Black White Blue Black Brown White Blue Black Solenoid valv...

Страница 250: ...the JIS stan dards for photoelectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions Solenoid valve etc 3 wire sensor with PNP output photoelectric sensor o...

Страница 251: ...mmunications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connec...

Страница 252: ...FF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 11 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Power supply short circuit detec tion Operates at 50 mA point min Dis...

Страница 253: ...ry switches is read when power is turned ON Internal Circuits CRT1 ID32S NPN Name LED status I O status Meaning 0 to 15 IN1 0 to 15 IN2 Lit yellow Input ON The input is ON Not lit Input OFF The input...

Страница 254: ...C G1 IN1 BS BDH BDL BS Photo coupler Photo coupler Input circuits Input circuits Internal circuits DC DC converter not isolated Physical layer Disconnection or short circuit detection circuit Disconne...

Страница 255: ...NC G1 IN 1 V NC G2 IN 2 V NC G3 IN 3 V NC G4 IN 4 V NC G5 IN 5 V NC G6 IN 6 V NC G7 IN 7 V NC G8 IN 8 1 2 V NC G9 IN 9 V NC G10 IN 10 V NC G11 IN 11 V NC G12 IN 12 V NC G13 IN 13 V NC G14 IN 14 V NC...

Страница 256: ...mmunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 257: ...5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection detec tion Operates at...

Страница 258: ...ss is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and 1 from left Output indicators 0 to 15 OUT1 Communications indicators M...

Страница 259: ...ide Right side V NC G OUT0 V G G V V NC G OUT0 V G G V Internal circuits DC DC converter not isolated Physical layer Voltage drop Voltage drop V V G G NC V G OUT0 V V G G NC V G OUT0 BS BDH BDL BS Pho...

Страница 260: ...sical layer Voltage drop Voltage drop Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit V V G G NC V G OUT0 V V G G NC V G OUT0 BS BDH BDL BS Photocoupl...

Страница 261: ...white Blue black 3 wire external device with NPN input Through beam emitter of photoelectric sensor Brown red Pink white Blue black 3 wire external device with NPN input Through beam emitter of photo...

Страница 262: ...mmunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Страница 263: ...pecification Model CRT1 MD32S CRT1 MD32S 1 CRT1 MD32SH CRT1 MD32SH 1 I O capacity 16 inputs Internal I O common NPN PNP NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 1...

Страница 264: ...G terminal 1 2 V max 0 5 A DC between each output ter minal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection...

Страница 265: ...output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status Meaning 0 to 15 inputs Lit red Short circuit detection The power supply is short c...

Страница 266: ...e Right side DC DC converter not isolated Physical layer Internal circuits Input circuits Voltage drop Short protection BS BDH BDL BS Photo coupler Photocoupler Left side Right side V NC G0 IN0 V NC G...

Страница 267: ...limit switch V NC IN 0 V NC G1 IN 1 V NC G2 IN 2 V NC G3 IN 3 V NC G4 IN 4 V NC G5 IN 5 V NC G6 IN 6 V NC G7 IN 7 V NC G8 IN 8 1 2 V NC G9 IN 9 V NC G10 IN 10 V NC G11 IN 11 V NC G12 IN 12 V NC G13 IN...

Страница 268: ...N 5 V6 NC G IN 6 V7 NC G IN 7 V8 NC G IN 8 1 2 V9 NC G IN 9 V10 NC G IN 10 V11 NC G IN 11 V12 NC G IN 12 V13 NC G IN 13 V14 NC G IN 14 V15 NC G IN 15 3 4 1 2 3 4 G V NC G OUT 8 NC G OUT 9 NC G OUT 10...

Страница 269: ...nications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector...

Страница 270: ...l 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Number of...

Страница 271: ...h and the 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 VID16ML NPN Name LED sta...

Страница 272: ...rter not isolated Physical layer Photo coupler 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Blue Black Brown White Blue Black Brown Red Black W...

Страница 273: ...ernally connected 3 wire sensor with PNP output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN 7 IN 6 IN 5 IN 4 IN 3 IN 2...

Страница 274: ...1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 5 3 78 7 60 15 21 5 92 8 85 7 1...

Страница 275: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 136 5 mm 48 10 mm 25 4...

Страница 276: ...See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5...

Страница 277: ...e 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 from mounted side Output...

Страница 278: ...VOD16ML 1 PNP BS BDH BDL BS Internal circuits Photo coupler Photo coupler V OUT0 OUT1 G DC DC converter not isolated Voltage drop Physical layer BS BDH BDL BS Photo coupler Photo coupler V OUT0 OUT1...

Страница 279: ...e the output power supply externally rather than from the terminals Solenoid valve etc Solenoid valve etc 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 G V G V OUT 7 OUT 6 OUT 5 OUT 4 OUT 3 OUT 2...

Страница 280: ...or install an ex ternal diode Dimensions Same for CRT1 VOD16ML and CRT1 VOD16ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable W...

Страница 281: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 136 5 mm 48 10 mm 25 4...

Страница 282: ...minal and the V terminal 17 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G...

Страница 283: ...set on the front side rotary switch The maximum node address is 62 The setting on the rotary switches is read when power is turned ON Input indicators I 0 to 15 II 0 to 15 Communications indicators M...

Страница 284: ...BS BDH BDL BS Photo coupler V IN0 IN1 G Input circuits Input circuits Internal circuits DC DC converter not isolated Physical layer Photo coupler BS BDH BDL BS Photo coupler V IN0 IN1 G Input circuits...

Страница 285: ...IN 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G...

Страница 286: ...N 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G V V IN 0 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G V V 2 wire sensor e g limit switch Brown W...

Страница 287: ...ions Same for CRT1 VID32ML and CRT1 VID32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug...

Страница 288: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Страница 289: ...ON simultaneously at an ambient operating temperature of 55 C When Units Are Mounted Facing Upwards If 32 points may be turned ON simultaneously the distance between the Units must be restricted depe...

Страница 290: ...n See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0...

Страница 291: ...on the front side rotary switch The maximum node address is 62 The setting on the rotary switches is read when power is turned ON Output indicators I 0 to 15 II 0 to 15 Communications indicators MS a...

Страница 292: ...VOD32ML 1 PNP BS BDH BDL BS Photo coupler V OUT0 OUT1 G Internal circuits DC DC converter not isolated Physical layer Photo coupler Voltage drop V OUT0 OUT1 G Voltage drop Internal circuits BS BDH BD...

Страница 293: ...0 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 G G V V G G V V OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT 0 2 3 4 5 6 7 8 9 10 11 12 1...

Страница 294: ...allocated words and bits when the first word for a Slave Unit allocated in the Master Unit is n 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 3...

Страница 295: ...ions Same for CRT1 VOD32ML and CRT1 VOD32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug...

Страница 296: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Страница 297: ...nsumption 45 mA max for 24 VDC power supply voltage 70 mA max for 14 VDC power supply voltage Weight 110 g max Item Specification Model CRT1 VMD32ML CRT1 VMD32ML 1 I O capacity 16 inputs Internal I O...

Страница 298: ...rrent 0 3 A output 2 A common See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage cu...

Страница 299: ...on the rotary switches is read when power is turned ON Internal Circuits CRT1 VMD32ML NPN Name LED status I O status Meaning I 0 to I 15 word m Lit yellow Input or output ON The input or output is ON...

Страница 300: ...nits with Connectors Section 5 4 CRT1 VMD32ML 1 PNP V1 IN0 G1 V2 OUT0 G2 BS BDH BDL BS Photo coupler Internal circuits DC DC converter not isolated Physical layer Photo coupler Voltage drop Input circ...

Страница 301: ...5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 G1 G1 V1 V1 G2 G2 V2 V2 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT 0 2 3 4 5...

Страница 302: ...as a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an ex ternal diode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 2...

Страница 303: ...RT1 VMD32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 0 1 2 3 4 5 6 7 8 9...

Страница 304: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Страница 305: ...ON simultaneously at an ambient operating temperature of 55 C When Units Are Mounted Facing Upwards If 16 points may be turned ON simultaneously the distance between the Units must be restricted depe...

Страница 306: ...and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 m...

Страница 307: ...and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08SL NPN Name LED status I O...

Страница 308: ...r to the revisions G V V G G V BS BDH BDL BS 0 to 7 Photocoupler Internal circuits DC DC converter not isolated Physical layer 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2...

Страница 309: ...ed Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Страница 310: ...e V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 8 outputs common Isolation method Photocoupler Output indicators LED yellow Installation...

Страница 311: ...1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD08SL NPN Name LED status I O status M...

Страница 312: ...al diode V G V V G G BS BDH BDL BS 0 to 7 Photo coupler Voltage drop Internal circuits Physical layer DC DC converter not isolated Solenoid valve etc 3 wire external device with NPN input Through beam...

Страница 313: ...hen a DCN4 TB4 Open Type Connector Is Mounted Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II...

Страница 314: ...ach input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current...

Страница 315: ...he 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 from left Input indicators 0...

Страница 316: ...rter not isolated G V 0 to 15 Phy sical layer Photocoupler G V G V BS BDH BDL BS Internal circuits DC DC converter not isolated V G 0 to 15 Phy sical layer Photocoupler V G V G 3 wire sensor with NPN...

Страница 317: ...r to the revisions Dimensions Same for CRT1 ID16SL and CRT1 ID16SL 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR...

Страница 318: ...Clamp Terminal Blocks Section 5 5 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 106 37 mm 45 5 48 10 m...

Страница 319: ...5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 16 outputs common Isolation method Photocoupl...

Страница 320: ...maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD16SL NPN Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The out...

Страница 321: ...not wire NC terminals BS BDH BDL BS Internal circuits V G 0 to 15 Physical layer Photocoupler V V G G Voltage drop DC DC converter not isolated Solenoid valve etc 3 wire external device with NPN input...

Страница 322: ...d Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Страница 323: ...em Specification Model CRT1 MD16SL CRT1 MD16SL 1 I O capacity 8 inputs Internal I O common NPN PNP ON voltage 15 VDC min between each input terminal and the V terminal 15 VDC min between each input te...

Страница 324: ...d the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per common 8 outputs common I...

Страница 325: ...n power is turned ON Internal Circuits CRT1 MD16SL NPN Name LED status I O status Meaning 0 to 7 inputs 0 to 7 outputs Lit yellow Input or output ON The input or output is ON Not lit Input or output O...

Страница 326: ...onverter non isolated Physical layer 0 to 7 Solenoid valve etc 3 wire external device with NPN input Through beam emitter of photoelectric sensor Brown white Black white Brown red Blue black Blue blac...

Страница 327: ...e force or install an ex ternal diode 3 Do not wire NC terminals 4 Wire colors have been changed according to revisions in the JIS stan dards for photoelectric and proximity sensors The colors in pare...

Страница 328: ...d Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Страница 329: ...Data 319 6 3 2 I O Data Type and Allocation 322 6 4 Status Areas 322 6 4 1 Analog Input Slave Unit Status Area 323 6 4 2 Analog Output Slave Unit Status Area 324 6 5 Analog Data Monitor 325 6 6 Units...

Страница 330: ...he speed of the conversion cycle 4 Moving average function Averages the most recent 8 values of the analog input value This provides a smooth input value for an input that oscillates Disabled Scaling...

Страница 331: ...n be utilized by the user reducing the calculation load on the ladder pro gram in the Master Unit Disabled 0 to 6 000 User adjustment Shift generated from measurement error due to hardware can be adju...

Страница 332: ...onverted to data from 0000 to 1770 Hex 0 to 6000 The input data range for which conversion is possible is 0 25 to 5 25 V and here the output data is FED4 to 189C Hex 300 to 6300 When input data is a n...

Страница 333: ...rom F448 to 0BB8 Hex 3000 to 3000 The input data range for which conversion is possible is 11 to 11 V and here the output data is F31C to 0CE4 Hex 3300 to 3300 When input data is a negative voltage it...

Страница 334: ...nected line input current is less than 3 04 mA a disconnected line detection function activates and data is set to 7FFF Hex Input Range Settings Setting of input range is performed using Analog Input...

Страница 335: ...conversion can be used to obtain the absolute value of the two s complement 6 2 2 Calculation and Selection Processing of Input Data Input Data Calculation The following types of calculations can be...

Страница 336: ...ing Trip Point High H Warning Trip Point Low L Alarm Trip Point Low LL can be performed Comparator function Input Moving average Scaling A A Analog input value Peak Bottom Top Valley Rate of change Cu...

Страница 337: ...top value valley value and rate of change is selected and allocated The default is allocation of the ana log value Note The comparator function can be used with regards to the value allocated to anal...

Страница 338: ...d select Parameters Edit from the pop up menu 3 Select the tab of the channel to select the analog data you want and select the type of allocation data from the Analog Data 1 Allocation pull down list...

Страница 339: ...Unit 2 Double click the icon of the Analog Input Unit to set in the Network Config uration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from t...

Страница 340: ...e one shot time can be changed For details refer to the one shot time set tings for the top valley hold function Analog Status Flags The Analog Status Flags include allocations for the Comparator Resu...

Страница 341: ...set ting 1 Lx Low Limit Alarm Flag Turns ON when the value of data allocated in Analog Data 1 drops below the Low Limit alarm setting 2 PSx Normal Flag pass signal Turns ON when none of the alarms Hi...

Страница 342: ...0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 Lower byte 9 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0 Upper byte 15 8 7 0 1 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 HD3 HD2 HD1 HD0 Lower byte 1 0 0 0 0 0 0...

Страница 343: ...low limit Output Range and Conversion Data Output Range 0 to 5 V Data of 0000 to 1770 Hex 0 to 6000 is converted to voltage from 0 to 5 V and output The output data range for which conversion is poss...

Страница 344: ...this case the output data becomes from 11 to 11 V Negative voltages are specified as two s comple ments 16 bits Output Range 4 to 20 mA Data of 0000 to 1770 Hex 0 to 6000 is converted to current from...

Страница 345: ...Integrator on page 481 regarding details for CX Inte grator 1 2 3 1 Turn ON the power to the CompoNet Slave Unit 2 Double click the icon of the Analog Output Unit to set in the Network Con figuration...

Страница 346: ...two s complements 6 4 Status Areas An Analog I O Slave Unit has two status areas the Warning Status Area and the Alarm Status Area The status flags in these areas are turned ON and OFF based on the th...

Страница 347: ...supply voltage is reduced below the set monitor value 3 Unit Maintenance Flag OFF Normal ON Error Higher than the monitor value Turns ON when the cumulative total unit conduction time exceeds the set...

Страница 348: ...g Hardware Error Flag OFF Normal ON Error Turns ON when there is an error in the analog circuits in the Unit 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Bit Content Descrip...

Страница 349: ...Integrator Monitor screen 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Bit Content Description Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Erro...

Страница 350: ...nit Con duction Time Displays the total time that the Unit has been ON cumulative power ON time Present Network Power Voltage Displays the present network power supply voltage Network Power Voltage Pe...

Страница 351: ...tab Buttons Clear Button Click this button to clear the displayed values Update Button Click this button to update the Maintenance informa tion Save Mainte nance Counter Button Click this button to sa...

Страница 352: ...eing held in the unit Min Value Status check boxes Over Range Turns ON if the analog data exceeds the upper limit of the displayable range High Alarm Over Turns ON if the analog data exceeds the set m...

Страница 353: ...d Cumu lated Counter Over Turns ON when the time integrated values increases above the monitor value set by the cumulated count function Cumulated Counter Overflow Selected when there is an overflow i...

Страница 354: ...ata 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 0000 to 1770 hex full scale 0 to 6 000 AD conversion range 5 FS of the above data ranges Isolation method Photocoupler isol...

Страница 355: ...ot be enabled 3 The DIP switch settings are read when the power is turned ON Input CH0 CH1 range common 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 1s digit of node address 10s digit of node address Pin N...

Страница 356: ...Circuits Terminal Arrangements Communications Connector Analog I O Terminal Block Input range Pin 4 Pin 5 Pin 6 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to...

Страница 357: ...ance 1 k min 600 max Resolution 1 6 000 full scale Overall accuracy 25 C 0 4 FS 0 4 FS See note 10 to 55 C 0 8 FS 0 8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F44...

Страница 358: ...DE ADR X10 0 63 X1 ON SW A D 1 2 3 4 5 6 7 8 INPUT RANGE CH0 1 INPUT RANGE CH2 3 RSV LSET 1 2 3 4 5 6 7 8 0 1 2 3 456 7 8 9 0 1 2 3 456 7 8 9 ANALOG TERMINAL CRT1 CRT1 DA02 DA02 DIP switch for setting...

Страница 359: ...ernal Circuits Wiring Communications Connector Output range Pin 1 Pin 2 Pin 3 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to 20 mA OFF OFF ON 0 to 20 mA ON OFF...

Страница 360: ...k Dimensions External device Output 1 Current output NC I0 V1 I1 1 NC V0 0 NC NC NC NC NC NC NC NC NC NC V0 V1 Voltage output terminal I0 I1 Current output terminal 0 1 Voltage current output terminal...

Страница 361: ...prox 250 Resolution 1 6 000 full scale Overall accuracy 25 C 0 3 FS 0 4 FS 10 to 55 C 0 6 FS 0 8 FS Conversion cycle 1 ms 1 point AD conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000...

Страница 362: ...is turned ON Input range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators MS and NS I O connector e CON connector Sensor power supply con...

Страница 363: ...se the CX Integrator rather than the DIP switch to make the settings 2 Do not set the DIP switches or pins other than as specified in the table above Sensor Power Supply Mode Settings Switch 4 Input C...

Страница 364: ...4 Input CH3 sensor power supply mode toggle Pin No Setting Specification 1 Input CH0 voltage current input mode toggle OFF Voltage input ON Current input Default setting is OFF 2 Input CH1 voltage cur...

Страница 365: ...sor power supply mode settings switch Analog GND 24 VDC Sensor power supply Sensor power supply connector Input type Sensor power supply mode settings switch Voltage Current input mode settings switch...

Страница 366: ...ON Power supply for 3 wire sensor ON Current input 24 VDC Sensor power supply n Voltage current input 0V Sensor power supply 4 3 2 1 n Voltage current input I O connector 24 VDC Sensor power supply 4...

Страница 367: ...Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted 92 8 85 7 102 96 7 90 90 101 7 5 3 6 4 23 60 66 2 mm The...

Страница 368: ...its with Connectors Section 6 7 When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 mm 136 5 mm 48 10 25 4 m...

Страница 369: ...8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 0000 to 1770 hex full scale 0 to 6 000 DA conversion range 5 FS...

Страница 370: ...t pin 8 to ON if the DIP switch is used to set the ranges If this pin is OFF the DIP switch settings will not be enabled 3 The DIP switch settings are read when power is turned ON 0 1 2 3 4 5 6 7 8 9...

Страница 371: ...to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to 20 mA OFF OFF ON 0 to 20 mA ON OFF ON Output range Pin 4 Pin 5 Pin 6 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10...

Страница 372: ...ng for Current Output Dimensions When a DCN4 TB4 Open Type Connector Is Mounted Analog GND In Vn n 3 4 2 4 3 2 1 External device I O connector 4 3 2 1 External device I O connector 92 8 85 7 102 96 7...

Страница 373: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is...

Страница 374: ...000 full scale Overall accuracy 25 C 0 3 FS 0 4 FS 10 to 55 C 0 6 FS 0 8 FS Conversion cycle 1 ms 1 point AD conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 00...

Страница 375: ...switch settings are read when power is turned ON Input range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators MS and NS Input range swit...

Страница 376: ...e the CX Integrator rather than the DIP switch to make the settings 2 Do not set the DIP switches or pins other than as specified in the table above Voltage Current Input Mode Settings Switch 4 Input...

Страница 377: ...t mode toggle 4 Input CH3 voltage current input mode toggle BS BDH BDL BS Communications power supply Communications data high Communications data low Communications power supply Pin No Signal name Pi...

Страница 378: ...250 n n Analog GND Voltage Current input mode settings switch Input type Voltage Current input mode settings switch Voltage input OFF Voltage input Current input ON Current input n RSV n AG n Voltage...

Страница 379: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is...

Страница 380: ...k min 600 max Resolution 1 6 000 full scale Overall accuracy 25 C 0 4 FS 0 4 FS See note 10 to 55 C 0 8 FS 0 8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F448 to 0...

Страница 381: ...ode address is 63 Rotary switch settings are read when power is turned ON Output range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators M...

Страница 382: ...or output CH1 See the next table Default setting All pins OFF 5 6 7 Always OFF Always set this pin to OFF Malfunctions may occur if it is set to ON 8 Range setting method OFF Use CX Integrator ON Use...

Страница 383: ...urrent Output Pin No Signal name Pin No Signal name 1 V0 Voltage output 2 V1 Voltage output 3 I0 Current output 4 I1 Current output 5 0 Voltage current output 6 1 Voltage current output 7 N C 8 N C 9...

Страница 384: ...Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted 92 8 85 7 102 96 7 90 90 101 7 5 3 6 4 15 60 78 73 mm The...

Страница 385: ...its with Connectors Section 6 7 When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 mm 136 5 mm 48 10 25 4 m...

Страница 386: ...362 Units with Connectors Section 6 7...

Страница 387: ...64 7 1 2 List of Data Processing Functions 364 7 1 3 Temperature Input Unit Display Modes 365 7 2 Overview of Temperature Input Units 367 7 2 1 Math Operations and Processing Input Data 367 7 2 2 I O...

Страница 388: ...aximum and minimum temperature input val ues Disabled Top valley hold Holds the top and valley temperature input values Disabled Rate of change Calculates the rate of change for temperature input val...

Страница 389: ...c imal place the value sent to the master will be 10 times the actual value The decimal point is omitted Example 1 R type thermocouple at 1 000 C 1 000 converted to hexadecimal 03E8 hex Example 2 U ty...

Страница 390: ...in the Network Configuration Window or right click the icon and select Parameter Edit to open the Configuration Window 3 Click the General Tab and select Temperature Data1 1 100 in the Default Connect...

Страница 391: ...h between values Treat any values displayed in Normal Display Mode beyond the specified input resolution as reference data 7 2 Overview of Temperature Input Units 7 2 1 Math Operations and Processing...

Страница 392: ...L and LL can be performed for Temperature Data 1 This is called the comparator function Flow of Data in Temperature Input Units In a Temperature Input Unit it is possible to switch the display mode of...

Страница 393: ...Display mode Set from CX Integrator 1 100 Display Mode 2 words input Temperature Data 1 allocated I O data Normal Display Mode 1 word input Data can be allocated for I O as Temperature Data 1 in eithe...

Страница 394: ...rate of change The temperature input value is allocated by default Note The comparator function can be used with the value allocated as Temperature Data 1 Top Valley Detection Timing Flags 1 input wor...

Страница 395: ...own in the following dia gram If the 1 100 Display Mode is set for the temperature input value with the CX Integrator eight words sixteen bytes will be allocated in the Master s Input Area as shown in...

Страница 396: ...he Default Con nection Path In Field The following example shows selecting the temper ature data and status flags 4 Click the Transfer PC to Unit Button to download the data and then click the Reset B...

Страница 397: ...ted in the Master Unit is shown below 2 words 4 bytes 15 0 First word 0CH Temperature Data 1 for Input CH0 First word 1CH Temperature Data 1 for Input CH1 First word 2CH Temperature Data 1 for Input C...

Страница 398: ...Low Limit alarm setting 1 Lx Low Limit Alarm Flag Turns ON when the value of data allocated in Temperature Data 1 drops below the Low Limit alarm setting 2 PSx Normal Flag pass signal Turns ON when n...

Страница 399: ...4 7 6 9 8 11 10 13 12 15 14 17 16 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Temperature Data 1 for Input CH0 Lower Word Lower byte 1 Upper byte 2 Temperature Data 1 for Input CH0 Upper Word L...

Страница 400: ...notices of the status flag in the Master Unit turns ON The Temperature Input Unit s status area information can be read by using the CX Integrator or explicit messages 15 8 7 0 1 0 Bit 7 Bit 6 Bit 5...

Страница 401: ...itoring 4 Reserved Cannot be used 5 Reserved Cannot be used 6 Reserved Cannot be used 7 Reserved Cannot be used 8 Temperature Input Warning Flag OFF Within range below set moni tor value ON Out of ran...

Страница 402: ...et monitor value Turns ON when the number of tops or valleys exceeds the set monitor value 13 Reserved Cannot be used 14 Reserved Cannot be used 15 Reserved Cannot be used Bit Content Description Bit...

Страница 403: ...has exceed the monitor value set by the Unit Conduction Time Monitor Function Network Power Voltage Drop Selected if the network power supply voltage has fallen below the monitor value set by the Net...

Страница 404: ...lue Displays the present temperature input value Peak Value Display the peak value bottom value top value and valley value of the temperature data retained by the Unit Bottom Value Top Value Valley Va...

Страница 405: ...er Selected when the cumulated time exceeds the monitor value set for the Cumulative Temperature Function Cumulative Counter Overflow Selected when there is an overflow in the cumu lative counter valu...

Страница 406: ...on Time Displays the total time that the network power supply had been ON when the error occurred Clear Button Clears the error history Item Specifications Model CRT1 TS04T CRT1 TS04P Input type Switc...

Страница 407: ...signals Photocoupler isolation Mounting method 35 mm DIN track mounting See note Communications power supply current 75 mA max at 24 VDC 110 mA max at 14 VDC 75 mA max at 24 VDC 110 mA max at 14 VDC W...

Страница 408: ...3 nodes can be set Note The rotary switch settings are read when the power is turned ON 0 1 2 3 4 567 8 9 0 1 2 3 4 567 8 9 T S S Communications connector Communications indicators MS and NS Node addr...

Страница 409: ...C or F display OFF C conversion ON F conversion Default setting OFF SW7 Always OFF Always set this pin to OFF Malfunctions may occur if it is set to ON SW8 Selects the input type set ting method OFF...

Страница 410: ...wer supply to the Temperature Input Unit 2 Double click the icon of the Temperature Input Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Confi...

Страница 411: ...ture range C Temperature range F Input type Temperature range C Temperature range F PT100 200 to 850 C 200 0 to 850 0 300 0 to 1 500 0 PT100 200 to 200 C 200 0 to 200 0 300 0 to 380 0 Input type C Dis...

Страница 412: ...on broken or disconnected input wire will be detected and the temperature data will be set to 7FFF Hex If the input temperature returns to the convertible range the off wire detection function will be...

Страница 413: ...detection wire the unused input terminals as shown in the following diagram Alternatively set the Input Error Detection Disable Function from the CX Integrator Dimensions Same for CRT1 TS04T and CRT1...

Страница 414: ...390 Temperature Input Units Section 7 5...

Страница 415: ...tion describes the Expansion Units 8 1 Expansion Units 392 8 2 Expansion Unit Specifications 394 8 2 1 Eight point Input Units 394 8 2 2 Eight point Output Units 397 8 2 3 Sixteen point Input Units 40...

Страница 416: ...properly mated I O Power Supply If an Expansion Input Unit is connected to a Digital Input Slave Unit then I O power must be supplied only to the Digital I O Slave Unit If any other combi nation of U...

Страница 417: ...le CRT1 ID16 XWT ID16 Not required The Expansion Unit uses the same I O power supply as the Digital I O Slave Unit Digital Input Slave Unit with Expan sion Output Unit Example CRT1 ID16 XWT OD16 Requi...

Страница 418: ...en each input terminal and the V terminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input te...

Страница 419: ...24 VDC 0 1 G Photocoupler Internal circuits Photocoupler V 24 VDC 0 1 G Photocoupler Internal circuits V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Brown White Blue Black 3 wire s...

Страница 420: ...ensors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for XWT ID08 and XWT ID08 1 V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Blue Black Brow...

Страница 421: ...outputs Rated output current 0 5 A output 2 0 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V te...

Страница 422: ...Specifications Section 8 2 Internal Circuits XWT OD08 NPN XWT OD08 1 PNP 0 1 G V 24 VDC Internal circuits Photocoupler Photocoupler Voltage drop 0 1 G V 24 VDC Internal circuits Photocoupler Photocou...

Страница 423: ...diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for XWT OD08 and XWT OD08 1 V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Solenoid v...

Страница 424: ...the V terminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal O...

Страница 425: ...circuits Photocoupler V 24 VDC 0 1 G Photocoupler Internal circuits Photocoupler V 10 1 11 3 12 5 13 7 14 9 15 G 0 2 3 4 4 6 5 8 6 24 VDC I O power supply 11 16 13 17 15 18 10 7 12 8 14 9 1 2 Brown Wh...

Страница 426: ...rentheses are the wire colors prior to the revisions Dimensions Same for XWT ID16 and XWT ID16 1 V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC 11 16 13 17 15 18 10 7 12 8 14 9 I O power...

Страница 427: ...ted output current 0 5 A output 4 0 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leak...

Страница 428: ...Specifications Section 8 2 Internal Circuits XWT OD16 NPN XWT OD16 1 PNP 0 1 G V 24 VDC Internal Circuits Photocoupler Photocoupler Voltage drop 0 1 G V 24 VDC Internal Circuits Photocoupler Photocou...

Страница 429: ...force or install an external diode Dimensions Same for XWT OD16 and XWT OD16 1 V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC 11 16 13 17 15 18 10 7 12 8 14 9 I O power supply Solenoid v...

Страница 430: ...406 Expansion Unit Specifications Section 8 2...

Страница 431: ...4 Two point Output Units IP54 423 9 3 5 Four point Input Units IP54 427 9 4 Clamp Terminal Blocks 432 9 4 1 Two point Input Two point Output Units IP54 432 9 5 Bit Slave Units with Compact Connectors...

Страница 432: ...Transmitted to Master Unit The Bit Slave Unit has two status areas the Warning Status Area and Alarm Status Area The status bit detection allocated to the master is OR of all slaves Bit Content Descri...

Страница 433: ...ocated four bits the input and output node address areas Two point Input Units Four point Input Units Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Error occurred Turns ON...

Страница 434: ...bit input area 0 is input Four point I O Units Bit Slave Units are allocated node address areas in order without leaving any bits unused in the middle For example eight two point Slave Units are allo...

Страница 435: ...apacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max be...

Страница 436: ...n the middle rotary switch and the 1s digit set on the right rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators 0 and 1...

Страница 437: ...l circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protection circuit DC DC converter not isolated Internal circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protectio...

Страница 438: ...nsors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02S and CRT1B ID02S 1 Brown Red Black White Blue Black 2 wire sensor e g limit switch 3 wire sens...

Страница 439: ...em Specification Model CRT1B OD02S CRT1B OD02S 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 2 A output Load power supply voltage Communications power supply voltage 0 V...

Страница 440: ...rotary switch and the 1s digit set on the right rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators 0 and 1 Power short...

Страница 441: ...D02S NPN Internal Circuits V NC BS BS BD H BD L NC OUT0 V NC NC OUT1 Load short circuit protection circuit Load short circuit protection circuit DC DC converter not isolated Internal Circuits NC NC BS...

Страница 442: ...a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for CRT1B OD02S and CRT1B OD02S 1 Solenoid valve etc Solenoid va...

Страница 443: ...B ID02SP CRT1B ID02SP 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G term...

Страница 444: ...it set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicator...

Страница 445: ...nal Circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protection circuit DC DC converter not isolated Internal Circuits BS BS BD H BD L V NC G IN0 V NC G IN1 DC DC converter not isolat...

Страница 446: ...colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02SP and CRT1B ID02SP 1 V NC G IN 0 V NC G IN 1 1 2 3 4 Brown Red Black White Blue Black 3 wire sensor wit...

Страница 447: ...l load current number of actuators used Item Specification Model CRT1B OD02SP CRT1B OD02SP 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 2 A output Load power supply volt...

Страница 448: ...set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Power short circuit indicator SHT0 Communications in...

Страница 449: ...OD02SP NPN Internal Circuits V NC BS BS BD H BD L NC OUT0 V NC NC OUT1 Load short circuit protection circuit DC DC converter not isolated Load short circuit protection circuit Internal Circuits G NC B...

Страница 450: ...id valve either use a built in diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for CRT1B OD02SP and CRT1B OD02SP 1 Solenoid valve etc Solenoid valve etc...

Страница 451: ...T1B ID04SP CRT1B ID04SP 1 I O capacity 4 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G te...

Страница 452: ...set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators...

Страница 453: ...Section 9 3 Internal Circuits CRT1B ID04SP NPN BS BS BD H BD L V0 NC G0 IN0 V0 NC G0 IN1 V1 NC G1 IN2 V1 NC G1 IN3 Load short circuit protec tion circuit Internal Circuits DC DC converter not isolate...

Страница 454: ...D L V0 NC G0 IN0 V0 NC G0 IN1 V1 NC G1 IN2 V1 NC G1 IN3 Internal Circuits DC DC converter not isolated Load short circuit pro tection circuit Load short circuit pro tection circuit V0 NC IN 0 V0 NC G0...

Страница 455: ...theses are the wire colors prior to the revisions Dimensions Same for CRT1B ID04SP and CRT1B ID04SP 1 V0 NC G0 IN 0 V0 NC G0 IN 1 V1 NC G1 IN 2 V1 NC G1 IN 3 1 2 3 4 Brown Red Black White Blue Black 3...

Страница 456: ...n Model CRT1B MD04SLP CRT1B MD04SLP 1 I O capacity 2 inputs Internal I O common line NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input term...

Страница 457: ...ly voltage 0 V max Communications power supply voltage 1 2 V min Residual voltage 1 2 V max 0 2 A DC between each output terminal and BS 1 2 V max 0 2 A DC between each output terminal and BS Leakage...

Страница 458: ...NPN Name LED status I O status Meaning 0 to 3 Lit yellow Input output ON The input output is ON Not lit Input output OFF The input output is OFF SHT0 Lit red Power short circuit detected The power sup...

Страница 459: ...G IN0 V NC G IN1 NC NC G OUT0 NC NC G OUT1 DC DC converter not isolated Load short circuit protection circuit Load short circuit protection circuit Load short circuit protection circuit V NC IN 0 V NC...

Страница 460: ...toelectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B MD04SLP and CRT1B MD04SLP 1 V NC G IN 0 V NC G IN 1 1 2 3 4 NC NC OUT 0...

Страница 461: ...ble I Multidrop Connector Plug at the location where a Bit Slave Unit with Compact Connectors is to be connected secure the extended cable with the terminal block so as not to cause a short circuit an...

Страница 462: ...ecification Model CRT1B ID02JS CRT1B ID02JS 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input t...

Страница 463: ...ll not be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation betwee...

Страница 464: ...ID02JS NPN CRT1B ID02JS 1 PNP BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 DC DC Conve...

Страница 465: ...lors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02JS and CRT1B ID02JS 1 G S V G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown w...

Страница 466: ...el CRT1B OD02JS CRT1B OD02JS 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 1 A output Load power supply voltage Communications power supply voltage 0 V max Communications...

Страница 467: ...t be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between dec...

Страница 468: ...02JS NPN CRT1B OD02JS 1 PNP BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 DC DC Con...

Страница 469: ...nals are shown below CRT1B OD02JS NPN CRT1B OD02JS 1 PNP Dimensions Same for CRT1B OD02JS and CRT1B OD02JS 1 G S V Solenoid valve etc G S V Signal Signal Emitter OFF input Photoelectric sensor emitter...

Страница 470: ...pecification Model CRT1B ID04JS CRT1B ID04JS 1 I O capacity 4 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input...

Страница 471: ...e performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decima...

Страница 472: ...ors Section 9 5 Internal circuits CRT1B ID04JS NPN BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 V2 IN2 G2 V3 IN3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Cont...

Страница 473: ...Connectors Section 9 5 CRT1B ID04JS 1 PNP BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 V2 IN2 G2 V3 IN3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continuous s...

Страница 474: ...lectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions G S V G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sens...

Страница 475: ...451 Bit Slave Units with Compact Connectors Section 9 5 Dimensions Same for CRT1B ID04JS and CRT1B ID04JS 1 20 6 65 24 62 9 mm...

Страница 476: ...del CRT1B OD04JS CRT1B OD04JS 1 I O capacity 4 outputs Internal I O common NPN PNP Rated output current 0 1 A output Load power supply voltage Communications power supply voltage 0 V max Communication...

Страница 477: ...formed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decimal nod...

Страница 478: ...with Compact Connectors Section 9 5 Internal circuits CRT1B OD04JS NPN BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 V2 OUT2 G2 V3 OUT3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit...

Страница 479: ...nnectors Pin arrangements and signals are shown below CRT1B OD04JS NPN BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 V2 OUT2 G2 V3 OUT3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit...

Страница 480: ...Compact Connectors Section 9 5 CRT1B OD04JS 1 PNP Dimensions Same for CRT1B OD04JS and CRT1B OD04JS 1 G S V G S V V G V G Solenoid valve etc Signal Signal Emitter OFF input Photoelectric sensor emitte...

Страница 481: ...ed Item Specification Model CRT1B MD02JS CRT1B MD02JS 1 I O capacity 1 input Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between eac...

Страница 482: ...V max DC 0 1 A between each output terminal and G terminal 1 2 V max DC 0 1 A between each output terminal and V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of...

Страница 483: ...ions will not be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation...

Страница 484: ...1B MD02JS NPN CRT1B MD02JS 1 PNP BS BDH BDL BS V IN0 G V OUT0 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V IN0 G V OUT0 G DC DC Converte...

Страница 485: ...G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch G S V G S V V...

Страница 486: ...462 Bit Slave Units with Compact Connectors Section 9 5 Dimensions CRT1B MD02JS and CRT1B MD02JS 1 15 21 65 24 48 9 mm...

Страница 487: ...d Item Specification Model CRT1B MD04JS CRT1B MD04JS 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between eac...

Страница 488: ...V max DC 0 1 A between each output terminal and G terminal 1 2 V max DC 0 1 A between each output terminal and V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of...

Страница 489: ...if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decimal node addre...

Страница 490: ...ectors Section 9 5 Internal circuits CRT1B MD04JS NPN BS BDH BDL BS V IN0 G V IN1 G V OUT0 G V OUT1 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continu...

Страница 491: ...act Connectors Section 9 5 CRT1B MD04JS 1 PNP BS BDH BDL BS V IN0 G V IN1 G V OUT0 G V OUT1 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continuous shor...

Страница 492: ...G S V Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch V G V G G S V G S V S...

Страница 493: ...469 Bit Slave Units with Compact Connectors Section 9 5 Dimensions Same for CRT1B MD04JS and CRT1B MD04JS 1 20 6 65 24 62 9 mm...

Страница 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...

Страница 495: ...471 SECTION 10 Repeater Units This section describes the Repeater Unit 10 1 Status Areas 472 10 2 Repeater Unit 474 10 2 1 Repeater Unit 474...

Страница 496: ...These bits indicate minor errors in the Unit Master Unit The Repeater Unit has two status areas the Warning Status Area and the Alarm Status Area Transmitted to Master Unit Repeater Unit The status b...

Страница 497: ...indicate serious errors in the Unit Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Error Turns ON when there is an error in the EEPROM data 2 Reserved 3 Reserved 4 Reserved...

Страница 498: ...r supply connector Note Communications power for the Repeater Unit is supplied from the BS and BS terminals on the upstream port communica tions connector PORT1 Communications power supply connector a...

Страница 499: ...cator status Status Meaning MS Lit green Normal status The Unit is operating normally Flashing green Lit red Fatal error A hardware error has occurred in the Unit The watchdog timer has timed out Flas...

Страница 500: ...mmunications Power Supply Connector This connector supplies communications power to Slave Units and Repeater Units connected to the downstream communications connector port 2 Note Communications power...

Страница 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...

Страница 502: ...478 Repeater Unit Section 10 2...

Страница 503: ...Monitor Digital I O Slave Units Only 495 11 3 2 Input Filter Input Units Only 496 11 3 3 Error Prevention for Surge Current at Startup Input Units Only 497 11 3 4 Contact Operation Monitor 498 11 3 5...

Страница 504: ...ld 546 11 6 5 Top Valley Counter 549 11 6 6 Rate of Change Calculation 550 11 6 7 Comparator 552 11 6 8 Temperature Range Count 556 11 6 9 Data Comparison between Channels 558 11 6 10 Input Error Dete...

Страница 505: ...it can be set or edited sim ply by double clicking on the Slave Unit in the Offline Window Refer to 11 2 Functions Common to All Slave Units for details on how to set and edit func tions for each Slav...

Страница 506: ...ay 2 Right click the network name in the Workspace Window and select Con nect from the pop up menu Toggles to on line status While connected online information on the CompoNet Slave Units is dis playe...

Страница 507: ...Operation Time Tab Pages More detailed maintenance information can be found on the OUT IN and Operation Time Tab Pages Online Connection Information Window Save Maintenance Counter Button The maintena...

Страница 508: ...484 CX Integrator Section 11 1...

Страница 509: ...485 CX Integrator Section 11 1...

Страница 510: ...h the Master Unit after the power is turned ON The baud rate setting is stored in memory until the power is turned ON again or until the Master Unit baud rate setting is changed 11 2 2 Hold Clear Outp...

Страница 511: ...n a status area in the Slave Unit will turn ON to notify the Master Unit The notification details can be read using the CX Integrator or using explicit messages Note 1 The minimum communications power...

Страница 512: ...time that power is ON i e the Total ON Time to the Slave Unit s internal circuits can be stored in the Slave Unit memory This data can be read using the CX Integrator or using explicit messages The mo...

Страница 513: ...e Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Click the General Tab Ente...

Страница 514: ...ower supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and sele...

Страница 515: ...h errors need to be identified The CX Integrator or explicit messages can be used to read write the name i e comment Settings Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet S...

Страница 516: ...ick the Reset Button to reset the Unit 6 Click the OK Button and exit the window 11 2 7 Communications Error History Monitor Description Enables storing the error communication failure details the com...

Страница 517: ...right click the icon for the desired CompoNet Slave Unit in the Network Configuration Window and select Monitor from the pop up menu 3 Click the Error History Tab in the Monitor Window The communicati...

Страница 518: ...ator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively rig...

Страница 519: ...fication details can be read using the CX Integrator or using explicit messages Note A detection voltage cannot be set for the I O power supply Checking Using the CX Integrator 1 2 3 1 Turn ON the pow...

Страница 520: ...ding pulses shorter than the communications cycle time set the OFF response time to a value longer than the communications cycle time The input may remain ON if the input pulse interval is too short S...

Страница 521: ...he I O power is turned ON i e until the Slave Unit stabilizes It helps avoid input errors caused by inrush current from con nected devices when the I O power supply is turned ON This function is enabl...

Страница 522: ...mory so once the number of contact operations reaches the monitor value a flag in a status area in the Slave Unit turns ON to notify the Master Unit The notification details can be read using the CX I...

Страница 523: ...value and then click the OK Button 5 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 6 Click the OK Button a...

Страница 524: ...for inputs of less than 1 s Measuring an ON Time of 0 5 s As shown in Figure A the actual ON time is 1 5 s 3 0 5 s but the total ON time is measured only as 1 s because the input is ON only once when...

Страница 525: ...lect Parameters Edit from the pop up menu 3 Click the IN Tab 4 Double click the I O Comment column for the terminal to be set The Edit Terminal Window will be displayed Select Time for the Detection M...

Страница 526: ...ication details can be read using the CX Integrator or using explicit mes sages The operation time is stored after the time lag from when the output turns ON until when the input turns ON is measured...

Страница 527: ...uble click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 C...

Страница 528: ...recover automati cally and power will be output to the connector where the short circuit was detected Note Use a power supply device with a rating of 100 W or higher as the communi cations power supp...

Страница 529: ...mation on load short circuit detection refer to the rated output current and internal circuits in the specifications for the applicable Unit An indicator on the Slave Unit can be used to see if a loa...

Страница 530: ...in Monitoring Status with the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Go online right click the icon of the applicable CompoNet Slave Unit in the Network Configurat...

Страница 531: ...is increased Setting Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open th...

Страница 532: ...inputs and uses the resulting value as conversion data When the input value fluctuates frequently as shown in the following diagram averaging can be used to produce a stable input value Setting Using...

Страница 533: ...user industry unit values Scaling also eliminates the need for ladder programming in the Master Unit to perform math operations The following two methods of input scaling can be used Default Scaling...

Страница 534: ...put between 28 000 to 28 000 but make sure that underflow or overflow does not occur The High Limit is 7FFE hex and the Low Limit is 8000 hex Note The offset value can be set even when using default s...

Страница 535: ...ration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the input where scaling is to be performed a...

Страница 536: ...e Scaling Point 100 Field 6 For offset compensation set the offset value in the Scaling Offset Field Either Default Scaling or User Scaling can be set in the Scaling Type Field 7 Return to the General...

Страница 537: ...erefore even when the Hold Flag is ON the first analog data transmitted to the Master Unit after the CPU Unit power is turned ON may be the data from when the Hold Flag was OFF To collect peak bottom...

Страница 538: ...the default connection path click the General Tab and select Holding Value from the pull down menu in the De fault Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the dat...

Страница 539: ...he Hold Flag is ON the first analog data transmitted to the Master Unit after the CPU Unit power is turned ON may be the data from when the Hold Flag was OFF To collect top valley hold data using the...

Страница 540: ...the default connection path click the General Tab and select Holding Value from the pull down menu in the Default Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the data...

Страница 541: ...ing for Setting Data Setting Hysteresis Using the CX Integrator 1 2 3 1 Input the value for hysteresis in the Hysteresis Field in the Top Valley Tab under the Function Choice heading 2 Return to the G...

Страница 542: ...ation Description The rate of change can be obtained for each sampling cycle set for the analog input data This function calculates the difference between each set sampling cycle and value obtained in...

Страница 543: ...et Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from t...

Страница 544: ...oint High H the Warning Trip Point Low L and the Alarm Trip Point Low LL When the analog data value exceeds the set value the Comparator Result Flag in the area for Analog Status Flags turns ON If an...

Страница 545: ...OFF delay can be set so that the Master Unit can receive notification of the Flag s status Setting Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click t...

Страница 546: ...input Functions Section 11 4 4 Click the Comparator Tab and set the four trip points The example here shows the setting for Alarm Trip Point High HH 5 To set the hysteresis value input the desired val...

Страница 547: ...ction is also used as the hys teresis value for the top valley hold function 6 To set the OFF delay function input the desired value in the Comparator Off Delay Field 7 Return to the General Tab Page...

Страница 548: ...4 to 20 mA input range a disconnected line is detected when the input current is below 3 04 mA 11 4 9 User Adjustment Description Depending on factors such as the characteristics and connection method...

Страница 549: ...nsmitted from the connected device to the Unit s input terminal that is equivalent to the 100 value 5 Click the Fix Upper Adjusting Value Button in the Adjustment Window and input the adjusted value 6...

Страница 550: ...minutes The count value is the analog input value in the industry unit obtained after scal ing For example 100 0 count hours indicates a value equivalent to an analog input value of 100 counts contin...

Страница 551: ...Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the input where the cumulated counte...

Страница 552: ...click the Cumulated Count Tab and input the de sired value in the Threshold Cumulated Counter Field 6 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then...

Страница 553: ...te from the Last Maintenance Date Field To enter the current date select Today from the bottom of the pull down menu 4 Click the Transfer PC to Unit Button to download the data and then click the Rese...

Страница 554: ...pecified scaling or industry specific units for output signal ranges The function eliminates the need for ladder programming in the Mas ter Unit to perform math operations The following two methods of...

Страница 555: ...and 28 000 but if underflow or overflow occurs in the scaled line the 100 or 0 output will not be possible The High Limit is 7FFE hex and the Low Limit is 8000 hex Note The offset value can be set ev...

Страница 556: ...nit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the output...

Страница 557: ...caling is selected set the 0 value in the Scaling Point 0 Field and set the 100 value in the Scaling Point 100 Field 6 For offset compensation set the offset value in the Scaling Offset Field Also sel...

Страница 558: ...be adjusted to compensate for error in the final output The following diagram shows when compensation is applied to the conversion line at the two points for 0 and 100 The ranges supported for adjust...

Страница 559: ...Adjust ment Button At this time set the output range Adjusting the Low Limit 4 Output the value from the Master Unit that is equivalent to 0 Always per form adjustment with the 0 value 5 Adjust the an...

Страница 560: ...peat adjustments until the correct 100 value is output from the output device After com pensation is completed click the Fix Upper Adjusting Value Button To return to the default settings click the De...

Страница 561: ...of 0 1 hours or minutes Monitor values can be set in the Slave Unit When the cumulated count value exceeds the set monitor value the Cumulated Counter Flag in the area for Generic Status Flags turns O...

Страница 562: ...To set the counter unit click the Cumulated Count Tab and select Hour or Minute from the pull down menu in the Cumulated Time Field 5 To set the monitor value click the Cumulated Count Tab and input t...

Страница 563: ...r a Unit error has occurred the current output will be 0 mA and the voltage output will be 0 V regardless of the setting Low limit Outputs the values in the following table according to the output ran...

Страница 564: ...sired item from the pull down menu in the Fault State Field 4 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit...

Страница 565: ...moving average processing is to be per formed and select the Moving Average Check Box in the Function Choice Area 4 Return to the General Tab Page click the Transfer PC to Unit Button to download the...

Страница 566: ...t occur The High Limit is 7FFE hex and the Low Limit is 8000 hex The High Limit is 7FFFFFFE Hex and the Low Limit is 80000000 Hex for 1 100 Display Mode Note The offset value can be set even when usin...

Страница 567: ...ure Input Unit Functions Section 11 6 4 Set 0 value in the Scaling Point 0 Field and set the 100 value in the Scaling Point 100 Field 5 To offset the scaled values set the offset value in the Scaling...

Страница 568: ...OFF The comparator function can be used to com pare the peak or bottom values allocated as temperature data 1 Refer to details on the comparator function Example of Bottom Hold Note A delay in network...

Страница 569: ...nput Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Configuration Window will be displayed 3 Click the tab for the input where peak bottom hol...

Страница 570: ...ram until notification of the flag s status is actually sent to the Slave Therefore even when the Hold Flag is ON the first temperature data transmitted to the Master Unit when the CPU Unit power is t...

Страница 571: ...fault Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 6 Click the OK Button and exit the window Hysteresis Setti...

Страница 572: ...C to Unit Button to download the data and then click the Reset Button to reset the Unit 3 Click the OK Button and exit the window Note The hysteresis set for the top valley hold function is also used...

Страница 573: ...en mainte nance is required for the Unit or sensor The status can be read in the Monitor Window or via an explicit message to know when the monitor value has been exceeded Valley Counter Operation Set...

Страница 574: ...tor value for the top valley counter 6 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 7 Click the OK Button...

Страница 575: ...ving average processing which will set a longer sampling cycle Setting Using CX Integrator 1 2 3 1 Turn ON the power supply to the Temperature Input Unit 2 Double click the icon of the Temperature Inp...

Страница 576: ...h Limit High Limit Low Low Limit and Low Limit are set in the Unit a status flag will be turned ON when a value exceeds the set range The four set values are High High Limit HH High Limit H Low Low Li...

Страница 577: ...is to stabilize the flag operation The setting range is 0 to 16 383 Note When setting the hysteresis value allow for the decimal point position or the 1 100 Display Mode for each input Always correct...

Страница 578: ...o the Temperature Input Unit 2 Double click the icon of the Temperature Input Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Configuration Win...

Страница 579: ...al point position Example Alarm value setting for 250 R thermocouple normal display setting 00250 decimal T thermocouple normal display setting 02500 decimal Setting for any input with 1 100 display 2...

Страница 580: ...Tab Page The temperature range boundaries are defined by the High High Limit HH High Limit H Low Low Limit LL or Low Limit L If the time within the set tem perature range exceeds the monitor value it...

Страница 581: ...guration Window will be displayed 3 Click the tab for the input where time is to be measured and select the Comparator Check Box in the Function Choice Area 4 Click the Comparator Tab and select the d...

Страница 582: ...t to detect an excessive temperature difference for preven tative maintenance in devices in which the temperature difference may cause or indicate a problem The comparison result can be checked in the...

Страница 583: ...arison Between Channels Tab 4 Double click the Calculation Data1 or Calculation Data2 cell to open the Edit Calculation Data Window 5 Select the two temperature inputs to be compared in the Calculatio...

Страница 584: ...led the temperature data is set to 7FFF hex 7FFF FFFFF when 1 100 Display Mode is being used 1 2 3 1 Turn ON the power supply to the Temperature Input Unit 2 Double click the icon of the Temperature I...

Страница 585: ...for each of the connected devices This enables the user to easily determine the next maintenance date The date can be set using the CX Integrator Setting Using CX Integrator Setting the last maintenan...

Страница 586: ...e the amount of heat endured by a sensor or device The cumulated value can be calculated in hours C hours or F hours or minutes C minutes or F minutes For example when the units are set to hours a cum...

Страница 587: ...w or right click the icon and select Parameter Edit The Configuration Window will be displayed 3 Click the tab for the input where the cumulated counter is to be set and select the Cumulated Count Che...

Страница 588: ...d value in the Threshold Cumulated Counter Field Note When the Threshold Cumulated Counter is set to 0 the cumulated value will not be monitored 6 Return to the General Tab Page click the Transfer PC...

Страница 589: ...hen absolutely necessary OMRON is not re sponsible for the results of user adjustments If a mistake is made in the adjustments the adjustment data can be cleared to return to the factory default setti...

Страница 590: ...junction compensator to disable it First adjustment Turn ON the power to the associated system devices Wait at least 30 minutes for the CRT1 TS04T s internal temperature to stabilize This stabilizatio...

Страница 591: ...ensors Use a cold junction compensator compatible with the sensor being adjusted Note When using an R S E B or W type thermocouple a K type can be substi tuted Set the ZERO CON to 0 C 32 F CX Integrat...

Страница 592: ...type to K 200 to 1 300 C 3 Connect the CX Integrator to the CompoNet network and go online 4 Upload settings to the CX Integrator 5 Turn ON the power supplies of all Units including the Temperature I...

Страница 593: ...alue 10 Adjust the upper limit value Input the upper limit voltage from the reference voltage current generator to the input terminals of the input to be adjusted Refer to the following table for the...

Страница 594: ...e Data 2 If the correct reference voltage was not input the adjustment values may not be accepted Adjusting the Bias Compensation Value 1 2 3 1 Disconnect the wiring for adjusting the upper and lower...

Страница 595: ...verify that the adjustments are correct Test the indication accuracy at three points the lower limit value an intermediate value and the upper limit val ue Connect the external devices as shown in th...

Страница 596: ...bilization time Input Unit s power supply ON Wiring for input 0 adjustment Input 0 upper lower limit adjustment Input 0 bias compensation Change wiring for input 1 adjustment Input 1 upper lower limit...

Страница 597: ...hen making adjustments Six dial Resistance Box and Precision Digital Multimeter These devices are used to make adjustments at the upper limit and lower limit Prepare devices that can provide accurate...

Страница 598: ...re Input Unit that is being adjusted 2 If the correct resistance cannot be obtained properly wire the digital mul timeter to the six dial resistance box and measure the resistance 3 Connect the CX Int...

Страница 599: ...ing Value Button in the Adjustment Window to write the adjustment value 10 Adjust the upper limit value Input the resistance from the six dial resis tance box Refer to the following table for the appr...

Страница 600: ...etails on the Monitor Win dow refer to 7 4 Monitoring Temperature Data Resetting Adjustments If it is necessary to reset the upper limit adjustment value and lower limit adjustment value to the factor...

Страница 601: ...Unit Functions Section 11 6 Note If the power supply is not turned OFF after making an adjustment it is not necessary to wait 30 minutes before continuing testing CRT2 TS04P Six dial resistance box In...

Страница 602: ...578 Temperature Input Unit Functions Section 11 6...

Страница 603: ...formation on maintenance that should be performed to ensure optimum application of the CompoNet Slave Units 12 1 Indicator Meanings and Troubleshooting 580 12 2 Troubleshooting 581 12 2 1 Troubleshoot...

Страница 604: ...Integrator to restore the default data Lit green Configuration error The same node address has been used more than once Repeater Unit configu ration error Check that the node address is set within th...

Страница 605: ...g used by more than one Slave Unit change the node address Refer to the next item The NS indicator lights green momentarily and then changes to red Replace the Slave Unit if its NS indicator is always...

Страница 606: ...he Network Power Voltage Drop Flag does not turn ON even if the network power sup ply voltage drops The monitor value for the net work power supply voltage is set too low Note The default setting is 1...

Страница 607: ...input filter is set there is a delay with the ON or OFF time The operation time ON or OFF edge selection may not be on the intended setting The selected operation time combination is not supported If...

Страница 608: ...even though the error has been fixed The status will not turn OFF until the power for the node where the error was detected is reset Cycle the communications power after fixing the error Slaves with...

Страница 609: ...then set the monitor value again The input s decimal point position for a Temperature Input Unit was in the wrong place when the monitor value was set Check the decimal point posi tion and enter the...

Страница 610: ...e sensor s decimal point position was read incorrectly The following conditions apply to the CRT1 TS04T only In 1 100 Display Mode the display value is multiplied by x100 regardless of the input type...

Страница 611: ...is the one word in the normal display area Either change the default con nection path to the 1 100 dis play area or select a connection path in the Master Unit for the 1 100 display area The temperatu...

Страница 612: ...ections should occur every 6 months to a year Periodic inspec tions should occur more frequently however for Units that are used in envi ronments subject to high temperatures high humidity or a lot of...

Страница 613: ...unctioning devices for repair attach a detailed description of the malfunction to the device and send the device to the OMRON representa tive listed at the end of this manual or to your OMRON represen...

Страница 614: ...590 Device Maintenance Section 12 3...

Страница 615: ...xplicit message and sends it to a CompoNet Slave Unit The response from the Slave Unit is then converted by the Master Unit from a CompoNet explicit message to a FINS response and sent back to the CPU...

Страница 616: ...cified for this parameter In a response the recep tion data defined for the service code is returned Number of Bytes Received Response The number of bytes received in the data from the destination nod...

Страница 617: ...ata is smaller than the specified size 0CFF Object state conflict The specified command cannot be executed due to an internal error 20FF Invalid parameter The specified operation command data is not s...

Страница 618: ...s 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for Unit Conduction Time unit 0 1 hr 10 hex 95 hex 01 hex 73 hex 4 bytes 0000000 0 to FFFFFFF F hex 0 to 4294967 295 Unit Main ten...

Страница 619: ...e ID 0E hex 08 hex 01 to 20 hex 68 hex 4 bytes 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for the total ON time unit s or number of contact operations unit opera tions of the...

Страница 620: ...0 hex 68 hex 4 bytes 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for the total ON time unit s or number of contact operations unit opera tion for the output No 1 to 32 specifie...

Страница 621: ...e Instance ID No 1 to 8 10 hex 97 hex 01 to 08 hex 67 hex 2 bytes See note Operation Time Moni tor Peak Value Read Read Reads the peak value for the time unit ms from the start point trigger until the...

Страница 622: ...01 hex Hold Setting for Output Sta tus Hold or Clear after Communi cations Error Write Sets whether hold or clear is set as the output status after a communi cations error for an out put No 1 to 32 s...

Страница 623: ...ex 1 byte 00 hex Dis abled Not used 01 hex Enabled Used Write Writes the unconnected line detection setting for the input No 1 to 32 specified by the Instance ID 10 hex 08 hex 01 to 20 hex 6B hex 1 by...

Страница 624: ...Command data Service data Attribute ID Data Load Short circuit Detection Status Read Reads the load short cir cuit status for the output No 1 to 32 specified by the Instance ID 0E hex 09 hex 01 to 20...

Страница 625: ...the output No 1 to 32 specified by the Instance ID 10 hex 09 hex 01 to 20 hex 6B hex 1 byte 00 hex Disabled Not used 01 hex Enabled Used Load Uncon nected Line Detection Status Read Reads the load un...

Страница 626: ...hex fixed 02 Response area 1 03 Response area 2 See note 1 Monitor Status for Total ON Time or Contact Operation Counter for All Slave Units Read at Once Read Reads the monitor sta tus for total ON ti...

Страница 627: ...the number of AD conversion points Write 10 hex Read 0E hex 0A hex 00 hex 64 hex 2 bytes 1 byte Input Range Set ting Write Read Sets the input range 10 to 10 V 0 0 to 5 V 1 0 to 10 V 2 4 to 20 mA 3 1...

Страница 628: ...hex 2 bytes 28000 to 28000 2 bytes 28000 to 28000 Maximum Value Read Read Reset Reads the maximum value after power is turned ON Read 0E hex Reset 35 hex 0A hex 01 to 04 hex 73 hex 2 bytes Minimum Val...

Страница 629: ...hex 0A hex 01 to 04 hex 8E hex 2 bytes Sampling Cycle Set ting Write Read Sets the sampling cycle for obtaining the rate of change based on the previous value Write 10 hex Read 0E hex 0A hex 01 to 04...

Страница 630: ...Write Read Default scaling 0 User scaling 1 Write 10 hex Read 0E hex 0B hex 01 to 02 hex 6F hex 1 byte Scaling Point 1 Set ting Write Read Sets a conversion value as the 0 value for user scaling Write...

Страница 631: ...1 hex 00 hex 64 hex 1 byte Tempera ture 1 Read for Normal Display Read Reads the value of tem perature data 1 0E hex 31 hex 01 to 04 hex A5 hex 2 bytes Tempera ture 1 Read for 1 100 Display Read Reads...

Страница 632: ...le 7 Write 10 hex Read 0E hex 31 hex 01 to 04 hex 6E hex 2 bytes 2 bytes Scaling Point 1 Set ting Write Read Sets an temperature value as the 0 value for user scaling Write 10 hex Read 0E hex 31 hex 0...

Страница 633: ...000 4 bytes 415000 to 415000 LL Value Setting Write Read Sets the LL value Write 10 hex Read 0E hex 31 hex 01 to 04 hex 12 hex 4 bytes 415000 to 415000 4 bytes 415000 to 415000 H Value Setting Write R...

Страница 634: ...0000 0 0000 0 1 0000 00 2 0E hex 31 hex 01 to 04 hex A3 hex 1 byte Top Valley Count Read Read Reset Reads the number of tops or valleys that have been counted Read 0E hex Reset 35 hex 31 hex 01 to 04...

Страница 635: ...ser set tempera ture range Write 10 hex Read 0E hex 31 hex 01 to 04 hex B0 hex 4 bytes 4 bytes Input Tem perature Variation Detection Read Read Reads the result of input temperature varia tion detecti...

Страница 636: ...mand data is read by using the EXPLICIT MESSAGE SEND command 28 02 The command data is written in words starting from D01000 in the CPU Unit and the response data is stored in words starting from D020...

Страница 637: ...0E Service code 0E hex D01003 00 95 Class ID 0095 hex D01004 00 01 Instance ID 0001 hex D01005 71 00 Attribute ID 71 hex The rightmost 00 hex is not read because the number of bytes of command data i...

Страница 638: ...a is received the lower byte is stored first S n 34 12 15 08 07 00 S n 12 34 15 08 07 00 S n 56 12 78 34 15 08 07 00 S n 78 34 56 12 15 08 07 00 Example for 1234 Hex Starting from the Upper Byte of I...

Страница 639: ...l Device type Product code Product name Basic Unit Expansion Unit CRT1 ID08 07 hex 1557 CRT1 ID08 CRT1 ID08 1 07 hex 1558 CRT1 ID08 1 CRT1 OD08 07 hex 1559 CRT1 OD08 CRT1 OD08 1 07 hex 1560 CRT1 OD08...

Страница 640: ...CRT1 MD16 1 CRT1 ROS08 07 hex 1593 CRT1 ROS08 CRT1 ROF08 07 hex 1594 CRT1 ROF08 CRT1 ROS16 None 07 hex 1511 CRT1 ROS16 XWT ID08 07 hex 1512 XWT ID16 07 hex 1513 XWT OD08 07 hex 1514 XWT OD16 07 hex 1...

Страница 641: ...16S 1 CRT1 ID16SH 07 hex 1599 CRT1 ID16SH CRT1 ID16SH 1 07 hex 1600 CRT1 ID16SH 1 CRT1 OD16SH 07 hex 1601 CRT1 OD16SH CRT1 OD16SH 1 07 hex 1602 CRT1 OD16SH 1 CRT1 MD16SH 07 hex 1579 CRT1 MD16SH CRT1 M...

Страница 642: ...SP 07 hex 1372 CRT1B ID04SP CRT1B ID04SP 1 07 hex 1373 CRT1B ID04SP 1 CRT1B MD04SLP 07 hex 1374 CRT1B MD04SLP CRT1B MD04SLP 1 07 hex 1375 CRT1B MD04SLP 1 CRT1B ID02JS 07 hex 1727 CRT1B ID02JS CRT1B ID...

Страница 643: ...ported Service Not supported Object instance Attribute Not supported Service Not supported Vendor specifica tion addition None Object class Attribute Not supported Service Not supported Object instanc...

Страница 644: ...H 1 CRT1 VID08S 1 CRT1 MD16S 1 CRT1 MD16SH 1 CRT1 ID08SL 1 CRT1 MD16SL 1 Assembly instance 5 16 inputs Input 7 6 5 4 3 2 1 0 CRT1 ID16 1 CRT1 ID16 1 XWT OD08 1 CRT1 ID16 1 XWT OD16 1 CRT1 OD16 1 XWT I...

Страница 645: ...VOD08S 1 CRT1 MD16S 1 CRT1 MD16SH 1 CRT1 OD08SL 1 CRT1 MD16SL 1 Assembly instance 35 16 outputs Output 7 6 5 4 3 2 1 0 CRT1 ID16 1 XWT OD16 1 CRT1 OD16 1 CRT1 OD16 1 XWT ID08 1 CRT1 OD16 1 XWT ID16 1...

Страница 646: ..._ST3 T_ST2 T_ST1 T_ST0 Instance 134 Analog Status Flags 0 BW0 T_ST0 V_ST0 HH0 H0 PS0 L0 LL0 CRT1 AD04 CRT1 VAD04S CRT1 VAD04ML 1 BW1 T_ST1 V_ST1 HH1 H1 PS1 L1 LL1 2 BW2 T_ST2 V_ST2 HH2 H2 PS2 L2 LL2 3...

Страница 647: ...12 Ch3 Temperature Data 1 13 14 15 Instance 122 Top Valley Detec tion Timing Flags 0 0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 CRT1 TS04T CRT1 TS04P 1 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0 Instance 134 Temperature D...

Страница 648: ...a 1 CRT1 TS04T CRT1 TS04P 1 2 3 4 Ch1 Temperature Data 1 5 6 7 8 Ch2 Temperature Data 1 9 10 11 12 Ch3 Temperature Data 1 13 14 15 16 0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 17 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0...

Страница 649: ...es No 82H Input and Mixed I O Slave Units 80H Output Slave Units and Repeater Units 4 Produced con nection ID Yes No 5 Consumed con nection ID Yes No 6 Initial comm characteristics Yes No 01 hexadecim...

Страница 650: ...3 0000 CRT1B ID04JS 1 Input Data 0001 0006 20_04_24_ 03_30_03 0000 CRT1B OD02JS 1 Output Data 0000 0001 0006 20_04_24_ 20_30_03 CRT1B OD04JS 1 Output Data 0000 0001 0006 20_04_24_ 21_30_03 CRT1B MD02J...

Страница 651: ...Data 0001 0006 20_04_24_ 04_30_03 0000 XWT ID16 1 Output Data 0000 0002 0006 20_04_24_ 23_30_03 Input Data 0002 0006 20_04_24_ 05_30_03 0000 XWT OD08 1 Output Data 0000 0003 0006 20_04_24_ 25_30_03 X...

Страница 652: ...20_04_24_ 05_30_03 0000 CRT1 OD16S 1 Output Data 0000 0002 0006 20_04_24_ 23_30_03 CRT1 MD16S 1 Input Data 0001 0006 20_04_24_ 04_30_03 0000 Output Data 0000 0001 0006 20_04_24_ 22_30_03 CRT1 ID16SH 1...

Страница 653: ...30_03 CRT1 MD16SL 1 Input Data 0001 0006 20_04_24_ 04_30_03 0000 Output Data 0000 0001 0006 20_04_24_ 22_30_03 CRT1 AD04 CRT1 VAD04S CRT1 VAD04ML Analog Data 1 0008 0006 20_04_24_ 68_30_03 0000 0000 G...

Страница 654: ...0002 0006 20_04_24_ 7A_30_03 0000 0000 Tempera ture Status 0004 0006 20_04_24_ 86_30_03 0000 0000 Tempera ture data 1 Normal Top and val ley shot 000A 0006 20_04_24_ AE_30_03 0000 0000 Tempera ture d...

Страница 655: ...V 85 mA max for 14 V CRT1 MD16 35 mA max for 24 V 60 mA max for 14 V CRT1 MD16 1 35 mA max for 24 V 60 mA max for 14 V CRT1 ROS08 95 mA max for 24 V 150 mA max for 14 V CRT1 ROF08 60 mA max for 24 V...

Страница 656: ...V CRT1 OD16TAH 1 40 mA max for 24 V 70 mA max for 14 V CRT1 MD16TAH 40 mA max for 24 V 70 mA max for 14 V CRT1 MD16TAH 1 40 mA max for 24 V 70 mA max for 14 V CRT1 VID08S 35 mA max for 24 V 50 mA max...

Страница 657: ...D32S 1 45 mA max for 24 V 70 mA max for 14 V CRT1 ID32SH 210 mA max for 24 V 235 mA max for 14 V CRT1 ID32SH 1 210 mA max for 24 V 235 mA max for 14 V CRT1 OD32SH 50 mA max for 24 V 90 mA max for 14 V...

Страница 658: ...50 mA max for 14 V CRT1 OD08SL 35 mA max for 24 V 55 mA max for 14 V CRT1 OD08SL 1 35 mA max for 24 V 55 mA max for 14 V CRT1 ID16SL 34 mA max for 24 V 55 mA max for 14 V CRT1 ID16SL 1 34 mA max for...

Страница 659: ...x for 24 V 80 mA max for 14 V CRT1B ID02S 1 45 mA max for 24 V 65 mA max for 14 V CRT1B OD02S 55 mA max for 24 V 75 mA max for 14 V CRT1B OD02S 1 55 mA max for 24 V 70 mA max for 14 V CRT1B ID02SP 65...

Страница 660: ...A max for 24 V 30 mA max for 14 V CRT1B ID04JS 35 mA max for 24 V 40 mA max for 14 V CRT1B ID04JS 1 35 mA max for 24 V 40 mA max for 14 V CRT1B OD04JS 30 mA max for 24 V 35 mA max for 14 V CRT1B OD04J...

Страница 661: ...sor s output residual voltage It is sometimes possible to satisfy the above equation by adjusting the I O power supply voltage VCC to 26 4 V Relation between ON Current of Slave Unit with DC Inputs an...

Страница 662: ...FF Ileak IOUT OFF current of a Slave Unit with DC Inputs Ileak Sensor s leakage current Connect a bleeder resistor if the Sensor s leakage current is greater than the OFF current of a Slave Unit with...

Страница 663: ...nals input current for number of points used cur rent supplied to input devices for number of points used I O power supply current consumption This value does not apply to 2 tier terminal block type s...

Страница 664: ...640 I O Power Supply Current Appendix E...

Страница 665: ...SV ON BIT NODE ADR 1 2 4 8 16 32 64 014 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 015 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 016 RSV ON BIT NODEADR 1 2 4 8 16 32 64 017 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 0...

Страница 666: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 049 RSV ON BIT NODEADR 1 2 4 8 16 32 64 050 RSV ON BIT NODEADR 1 2 4 8 16 32 64 051 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 052 RSV ON BIT NODEADR 1 2 4 8 16 32 64 053...

Страница 667: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 084 RSV ON BIT NODEADR 1 2 4 8 16 32 64 085 RSV ON BIT NODEADR 1 2 4 8 16 32 64 086 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 087 RSV ON BIT NODEADR 1 2 4 8 16 32 64 088...

Страница 668: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 113 RSV ON BIT NODEADR 1 2 4 8 16 32 64 114 RSV ON BIT NODEADR 1 2 4 8 16 32 64 115 RSV ON BIT NODEADR 1 2 4 8 16 32 64 116 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 117...

Страница 669: ...g 3 communications power supply 85 comparator 4 520 Comparator Result Flag 552 553 CompoNet networks 32 Configurator writing maintenance dates 561 connection object 625 contact operation monitor 2 498...

Страница 670: ...moving average processing 508 MS indicators 580 Multi power Supply Slave Units 85 N naming connected devices 3 491 naming Units 3 490 Network Power Supply Slave Units 86 network power voltage monitor...

Страница 671: ...ard Window 481 static electricity xxii status areas 120 322 392 408 472 Alarm Status Area 121 324 325 409 473 Warning Status Area 120 323 324 408 472 T Temperature Data Status Flag 370 373 Terminating...

Страница 672: ...648 Index...

Страница 673: ...outputs with 2 tier terminal block and SSR outputs with 3 tier termi nal block with e CON connector or with screwless clamp terminals 8 point Input 8 point Output Units with 2 tier terminal block wit...

Страница 674: ...650 Revision History...

Страница 675: ...rg IL 60173 5302 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711...

Отзывы: