117
Basic Specifications of Slave Units
Section 4-1
4-1-2
Performance Specifications
Note
Applicable only to Slaves to which screw terminal blocks are mounted.
Some of the specifications are different for the CRT1-ROS08/ROS16 (with
relay outputs) and the CRT1-ROF08/ROF16 (with SSR outputs). For details,
refer to
5-3-8 Sixteen-point Output Units (2-tier Terminal Block with Relay Out-
puts)
and
5-3-9 Sixteen-point Output Units (2-tier Terminal Block with SSR
Outputs)
.
4-1-3
Communications Indicators
The communications indicators have the following meanings.
MS (Module Status): Indicates the status of the node with a two-color LED
(green/red).
NS (Network Status): Indicates the status of communications with a two-color
LED (green/red).
Item
Specification
Communications power supply voltage 14 to 26.4 VDC
I/O power supply voltage
20.4 to 26.4 VDC (24 VDC
−
15%/+10%)
Noise immunity
Conforms to IEC 61000-4-4, 2 kV (power line).
Vibration resistance
10 to 60 Hz with double-amplitude of 0.7 mm, 60 to 150 Hz and 50 m/s
2
in X, Y,
and Z directions for 80 min each
Shock resistance
150 m/s
2
(3 times each in 6 directions on 3 axes)
Dielectric strength
500 VAC (between isolated circuits)
Insulation resistance
20 M
Ω
min. (between isolated circuits)
Ambient operating temperature
−
10 to 55
°
C
Ambient operating humidity
25% to 85% (with no condensation)
Ambient operating atmosphere
No corrosive gases
Storage temperature
−
25 to 65
°
C
Storage humidity
25% to 85% (with no condensation)
Terminal block screw tightening torque
(See note.)
M3 wiring screws: 0.5 N
⋅
m
M3 mounting screws: 0.5 N
⋅
m
Installation
Mounting with 35-mm DIN Track, M4 screws, or Mounting Brackets (depending
on model)
Name
Indicator status
Node/communications
status
Meaning
MS
Lit green.
Normal status
The Unit is operating normally.
Lit red.
Fatal error
A hardware error has occurred in the Unit. The watchdog
timer has timed-out.
Flashing red.
Non-fatal error
There is an error in the switch settings.
An EEPROM checksum error has occurred.
Not lit.
Power OFF/Startup
The power supply is OFF, the Unit is being reset, or the Unit
is being initialized.
Содержание CRT1 - 10-2009
Страница 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...
Страница 2: ......
Страница 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ...x...
Страница 16: ...xvi...
Страница 24: ...xxiv Conformance to EC Directives 6...
Страница 386: ...362 Units with Connectors Section 6 7...
Страница 414: ...390 Temperature Input Units Section 7 5...
Страница 430: ...406 Expansion Unit Specifications Section 8 2...
Страница 486: ...462 Bit Slave Units with Compact Connectors Section 9 5 Dimensions CRT1B MD02JS and CRT1B MD02JS 1 15 21 65 24 48 9 mm...
Страница 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...
Страница 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 502: ...478 Repeater Unit Section 10 2...
Страница 508: ...484 CX Integrator Section 11 1...
Страница 509: ...485 CX Integrator Section 11 1...
Страница 602: ...578 Temperature Input Unit Functions Section 11 6...
Страница 614: ...590 Device Maintenance Section 12 3...
Страница 664: ...640 I O Power Supply Current Appendix E...
Страница 672: ...648 Index...
Страница 674: ...650 Revision History...