60
DM Area Allocation in Gate, Cumulative Gate, and Sam-
Section 5-4
5-4
DM Area Allocation in Gate, Cumulative Gate, and
Sampling Modes
The section explains DM and IR bit allocation in gate, cumulative gate, and
sampling modes.
DM Allocation
Word
Bit
Function
m
00 to 03
Operating mode (4: Gate mode; 5: Cumulative gate mode; 6: Sampling mode)
04 to 07
Not used.
08 to 11
Not used.
12 to 15
Counter value (0: BCD; 1: Hexadecimal)
m+1
00 to 03
04 to 07
08 to 15
Not used.
m+2
00 to 15
Counter 2 input types and control mode:
Input types
Refer to the information on counter 1 input types and control mode.
Counter 2 control mode
The following bits are used for the internal control inputs.
Word n bit 10: Internal control IN1
Word n bit 11: Internal control IN2
m+3 to
m+99
00 to 15
Not used.
Counter 1 input types and control mode:
Input types
0: x 1
1: x 2
2: x 4
3: Up and down pulses input
4: Pulse and direction input
Offset phase inputs (counter 1)
Counter 1 control mode
Set control inputs IN1 and IN2 to external control inputs IN1 and IN2 or internal control inputs IN1
and IN2.
The following bits are used for the internal control inputs.
Word n bit 08: Internal control IN1
Word n bit 09: Internal control IN2
0: External inputs (connector inputs)
1: Internal inputs (data area inputs)
0: External control inputs IN1 and IN2
1: Internal control inputs IN1 and IN2