![Omron C200H-CT021 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/omron/c200h-ct021/c200h-ct021_operation-manual_741966021.webp)
8
Specifications
Section 2-1
Output Characteristics
The maximum switching current depends upon the power supply voltage, as
shown below.
Note
The output current must not exceed 0.5 A per common (i.e., eight points), oth-
erwise the built-in fuse will blow out. The built-in fuse cannot be replaced by
the user.
Item
External Outputs 0 to 7
Max. switching capacity
16 mA at 4.5 VDC to 80 mA at 26.4 VDC
(See the following graph.)
320 mA max./common
Leakage current
0.1 A max.
Residual voltage
0.8 V max.
ON/OFF response time
0.2 ms max.
External power supply
5 to 24 VDC
±
10% (50 mA max. at 26.4 VDC)
(VDC)
80
50
16
External power supply voltage
Maxim
um s