13
High-speed Counter Unit Components
Section 2-2
2-2-3
Switch Settings
There are two rotary switches on the front panel of the High-speed Counter
Unit, which can be used for unit number and operating mode settings.
Note
1.
Be sure to turn OFF the High-speed Counter Unit before setting the unit
number and operating mode.
2.
Use a flat-blade screwdriver for rotary switch settings.
3.
Be sure not to damage the grooves of the rotary switches with the flat-
blade screwdriver. Do not leave either of the rotary switches set midway
between numbers. Otherwise a setting error may occur.
Note
The unit number must not be same as the unit number of any other Special I/
O Unit or Position Control Unit in the same system, otherwise a setting error
will result. Each unit number in the system must be unique.
The unit number can be set within a range of 0 to 9 if the C200H, C200HS,
C200HE-CPU11/32/42(-Z), C200HG-CPU33/43(-Z), or C200HX-CPU34/44(-
Z) is used with the High-speed Counter Unit.
The operating mode must be set within a range of 0 to 6. Do not set the oper-
ating mode to 7, 8, or 9, otherwise the High-speed Counter Unit will not oper-
ate.
2-2-4
Rear Setting Switch
The rear setting switch of the High-speed Counter Unit is used to select the
output mode.
Switch
Setting
Function
MACHINE No.
Unit number setting
Set the switch within a range of 0 to F.
MODE
Operating mode set-
ting
Set the switch within a range of 0 to 6.
0: Simple counter mode
1: Linear mode
2: Circular mode
3: Preset mode
4: Gate mode
5: Cumulative gate mode
6: Sampling mode
7 to 9: Not used
Switch
Function
NPN
Outputs 0 to 7 will be NPN outputs.
PNP
Outputs 0 to 7 will be PNP outputs.