![Omron C200H-CT021 Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/omron/c200h-ct021/c200h-ct021_operation-manual_741966128.webp)
121
Types of Data Written with IOWR Instruction
Section 10-3
Gate, Cumulative Gate,
and Sampling Modes
OK: Possible
NG: Not possible
10-3 Types of Data Written with IOWR Instruction
This section describes data transfer and types of data written with the IOWR
instruction in each mode.
Simple Counter Mode
Linear and Circular Modes
DM
Set item
IORD instruction control code
IOWR instruction control code
#00XX
#CCXX
#00XX
#CCXX
#FX00
---
XX = 0 to 99
---
XX = 0 to 99
---
m
Operating mode
NG
OK
NG
NG
---
m+1
Counter 1 input
NG
OK
NG
NG
---
m+2
Counter 2 input
NG
OK
NG
NG
---
m+3 to
m+99
Not used
NG
OK
NG
OK
---
Present counter value
---
---
---
---
NG
DM
Set item
Data transfer
IOWR instruction
m
Operating mode
Not available
Not available
Present counter value
Not available
Available
DM
Set item
Data transfer
IOWR instruction
m
Operating mode
Not available
Not available
m+1
Counter 1 input
Not available
Not available
m+2
Counter 2 input
Not available
Not available
m+3
First word number of block of words
storing data transferred
Not available
Available
m+4
Number of data blocks transferred
Not available
Available
m+5
Counter 1 ranges enabled
Not available
Available
m+6
Counter 2 ranges enabled
Not available
Available
m+7 to m+8
Counter 1 maximum count value
Not available
Available
m+9 to m+10
Counter 2 maximum count value
Not available
Available
m+11 to m+14
Not used
Not available
Not available but no error results
m+15 to m+19,
to
m+90 to m+94
Ranges 0 to 15
Available
Available
m+95 to m+99
Not used
Not available
Not available but no error results
Present counter value
Available
Available
Содержание C200H-CT021