4 Replacing the battery
4-2 Replacing the battery
BU100RS
64
4-2 Replacing the battery
The battery can be replaced while the unit is stopped (power supply output stopped).
Refer to the below-shown reference data “life of the battery” for the details about the life of
the battery.
Caution
(for battery replacement)
Risk of explosion if battery is replaced by an incorrect type.
When replacing batteries replace with the same type and
number of batteries or battery packs.
Notes
●
Be sure to reset the battery life counter after replacing the battery.
Press and hold the “Buzzer Pause/Test” switch of the UPS for 10 seconds or
longer to reset the battery life counter. Resetting is complete when “bJ” is
displayed.
* Perform a reset with the “AC input” ON.
・
Stopping (“Power” switch OFF): When the beeper becomes a sustained beep,
release the switch.
・
In Commercial Power Mode (“Power” switch ON): When the beeper changes from
intermittent beeps to a sustained beep, release the switch.
If you do not reset the battery life counter, a battery deterioration alarm may occur
faster than the expected battery life.
●
When the unit is used in compliance with UL standards, battery replacement
should be performed or supervised by personnel familiar with the danger of
batteries and the required precautions.
●
If you replace the battery while operating, please conduct a self-diagnostic test.
Press "buzzer stop / test" switch for 5 seconds to 9 seconds and release the
switch when the buzzer beeps (intermittent sound). After the self-diagnostic test is
started and the test is completed, it automatically returns to the operation mode.
●
If an input power supply error such as a power failure occurs when replacing the
battery while in operation, backup cannot be performed and output stops.
●
Do not replace the battery while the UPS is operating in backup mode. Output will
stop.
Additional Information
When the battery replacement LED lights up/blinks and beeper sounds, press the “Buzzer
Pause/Test” switch for 0.5 to 4 seconds to stop the beeper. (Lighting/blinking of “battery
replacement” LED does not disappear.)
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......