3 Check and start operation
3-1 The name and function for the operation and display
BU100RS
42
7 OFF, 8 OFF: Commercial synchronous operation (ECO mode disabled)
・
Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
・
Output frequency: Output in synchronization with input frequency.
・
Bypass output: Bypass output in the event of failure or overload.
7 OFF, 8 ON: Commercial synchronous operation (ECO mode enabled)
・
Output voltage: Input voltage is output as it is in Commercial Power Mode. (Low
power consumption due to bypass output). Input voltage is output as it is.
・
Output frequency: The same as the input frequency due to normally bypass
output in Commercial Power Mode.
Note: When ECO mode enabled, after 5 minutes if the grid is within the voltage/frequency range of
ECO mode (see the table below), UPS will transfer to ECO mode and working in the bypass.
Table: ECO mode range
Input AC Voltage
+/-10% of the nominal output voltage
Input AC Frequency(50Hz mode)
45.5
~
54.5Hz+/-0.5
%
Input AC Frequency(60Hz mode)
55.5
~
64.5Hz+/-0.5
%
7 ON, 8 OFF: Asynchronous operation (50 Hz output)
・
Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
・
Output frequency: Always output with 50 Hz. It is not affected by input
frequency.
・
Bypass output: An output stops without bypass output in the event of failure or
overload.
7 ON, 8 ON: Asynchronous operation (60 Hz output)
・
Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
・
Output frequency: Always output with 60 Hz. It is not affected by input
frequency.
・
Bypass output: An output stops without bypass output in the event of failure or
overload.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......