2 Installation and connection
2-3 Connecting the AC input
BU100RS
36
2-3 Connecting the AC input
1.
When you connect it to a commercial power source, battery charging automatically
starts regardless of the ON/OFF state of the “Power” Switch and charging completes
within 8 hours.
Load
Isolator switch or circuit breaker
100VAC (Example of connection)
* When in use, make sure the terminal block
cover is attached.
Commercial
power source
AC input plug
Caution
To reduce the risk of fire,
●
Connect only to a circuit provided with 15A maximum branch circuit overcurrent
protection in accordance with the National Electric Code, ANSI/NFPA 70 and the
Canadian Electrical Code, Part I, C22.1.
For Pluggable Equipment – The socket-outlet shall be installed near the equipment
and shall be easily accessible.
●
Provide an emergency stop switch or an externally-installed breaker on the external
output side.
Reference
●
The unit was charged before shipment, but it may have self-discharged during shipment,
resulting in a reduced backup time. We recommend charging the unit before use.
●
You can perform "3-2 Checking the operation " also before charging the battery.
When installation and connection are complete, connect the unit’s AC input plug to a
commercial power source.
Make sure to connect the AC input of the unit into a wall outlet
(commercial power source) with rated input voltage of 100/110/115/120V
AC.
●
Connecting to a wall outlet (commercial power source) of a different rated voltage
may result in fire.
●
The unit may fail.
For other cautions when connecting the UPS, refer to “Caution (for installation and
connection)” shown in the “Safety precautions” of the beginning of this manual.
Installation and connection is now complete.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......