3 Check and start operation
3-1 The name and function for the operation and display
BU100RS
41
3
2) When BS signal is used to shut down the UPS when AC input is ON
1 sec
AC input
Power output
(Setting switch 4 OFF:
Mode A)
Power output
(Setting switch 4 ON:
Mode B)
BS signal
*1
Starts up when BS signal
turns OFF
Starts up whenAC input
turns from OFF to ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
*1 For 10 seconds as a default setting.
●
Logic of Remote on/off signal
(
“
Setting
”
switch 5)... Factory setting: OFF
OFF: UPS start shutdown process when detecting close condition of remote input signal.
ON: UPS start shutdown process when detecting open condition of remote input signal.
●
Synchronous/asynchronous operation setting
(
“
Setting
”
switch 7, 8)... Factory setting: Refer to the table below.
“Setting” switch 7
“Setting” switch 8
Operating mode
OFF
OFF
Commercial synchronous operation
(ECO mode disabled)
OFF
ON
Commercial synchronous operation
(ECO mode enabled)
ON
OFF
Asynchronous operation
(50 Hz output)
ON
ON
Asynchronous operation
(60 Hz output)