![Omron BU100RS Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/omron/bu100rs/bu100rs_instruction-manual_744588049.webp)
3 Check and start operation
3-3 Start and stop procedures and basic operation
BU100RS
48
■
Operation when using
You may either leave the “Power” switch of the unit ON (operation status) or turn it OFF
each time when stopping the connected system. Choose whichever operation method is
more convenient.
We recommend turning OFF the “Power” switch when you do not use connected devices
for a long time.
The battery can be charged once the AC input terminal is connected to a commercial
power source.
■
Operation after a power failure
・
If a power failure or abnormal input power supply occurs, the UPS automatically
switches to Battery Mode, continuing power output from the Power Supply Output
Receptacles and output terminal block supplied from the battery.
・
The status is displayed and the beeper sounds intermittently to alert the user.
See also “Setting” switch 1 can be used to turn the beeper ON/OFF.
( indicates blinking)
Icon
Beep
Output
Description
Intermittent
4-second intervals
ON
Backup is operating due to power failure or AC input error.
Output will stop if Battery Mode continues.
Intermittent
1-second intervals
ON
Backup is operating due to power failure or AC input error.
Battery level is low, so output will stop soon.
None
OFF
Battery is dead, so output stopped.
■
Operation when a power failure is recovered
●
When charge of the battery remains
The unit automatically resumes output via commercial power if it recovers from a power
failure/input power supply error while Backup is operating. The spent battery starts
charging.
●
When charge of the battery does not remain
If a power failure or abnormal power input is resolved after the battery is discharged
completely and power output is stopped, the UPS restarts automatically and resumes
power output. The expended battery begins to charge.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......