3 Check and start operation
3-5 UPS operation mode settings
BU100RS
55
3
3-5 UPS operation mode settings
3-5-1 Settable items and explanations
There are seven items to select.
1) Output voltage setting
2) Maximum backup time setting
3) Reboot battery voltage setting
4) BS signal delay setting
5) BU signal delay setting
6) Dry contact logic setting
7) Dry contact test
The settings available for this operation are shown below.
1. Output voltage setting (100V/110V/115V/120V)
Four types of output voltage can be set. (Setting range: 100V/110V/115V/120V,
Default setting: 100V)
Output is performed at the set voltage, with no relation to the input voltage.
2. Maximum backup time setting
Maximum backup time can be set. (Setting range: 0 to 90 minutes, Default
setting: 0 minute)
3. Reboot battery voltage setting
The limit battery capacity for wake-up can be set. (Setting range: 0 to 90%,
Default setting: 0%)
4. BS signal delay setting
It is possible to set the delay time for stopping the power supply output after the
BS signal is received. (Setting range: 0 to 10 minutes, Default setting: 0 minute)
This timing is 10 sec.
Power output stop decay
ON
ON
ON
OFF
OFF
OFF
AC input
BS signal
Power supply
output
5. BU signal delay setting
It is possible to set the delay time of BU signal after AC fail occur.
(Setting range: 0 to 90 seconds, Default setting: 0 second)
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......