6 Contact signal functions
6-1 Contact signal functions
BU100RS
82
6-1-7 Example of the use of the Contact Signal circuit
●
Example of BU signal output circuit and
the connected circuit
●
Example of BS signal input circuit
and the connected circuit
To port
on PC
4.7K
TLP521
Inside of
UPS
External
Circuit
+12V
1K
Ω
C2
C1
+5V
C1,C2 : 0 pF to several
thousand pF
(Consider the capacity according to the
operating environment.)
*
COM
UPS side
GND
C2458
BS
From port on PC
12V
1K
1.2K
TLP521
System side
Connecting cable
(twisted or shielded)
●
Remote ON/OFF circuit
Example of
remote
ON/OFF
Remote
ON/OFF (+)
Remote
ON/OFF (-)
UPS side
6-1-8 Precautions and notes for the use of the Contact
Signal
Notes
When connecting a device such as a relay that generates counter
electromotive force to the signal output circuit, connect diodes that prevent
counter electromotive force to both ends of the relay.
Explanation:
●
When power is restored after the unit stopped automatically during a power failure,
the unit automatically restarts and supplies power. If you do not want to start the
connected devices, turn OFF their switches or set the auto startup setting after
recovery from power failure (“Setting” switch 2) to ON (Auto startup is not
performed).
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......