![Omron BU100RS Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/omron/bu100rs/bu100rs_instruction-manual_744588071.webp)
4 Replacing the battery
4-2 Replacing the battery
BU100RS
70
8.
Attach the front panel to the unit.
Insert the tab on the left side of the front panel into the hole in the main unit, and push
the front panel towards the main unit. (1
Use a hex screwdriver or wrench to securely tighten (clockwise) the 2 screws at the top
of the front panel. (2
2
Tighten the 2 screws
with hex screwdriver
or wrench
1
Insert the tab on the left
into the main unit
Battery replacement is now complete.
Notes
Be sure to reset the battery life counter after replacing the battery.
●
Press and hold the “Buzzer Pause/Test” switch of the UPS for 10 seconds or
longer to reset the battery life counter. Resetting is complete when “bJ” is
displayed. * Perform a reset with the “AC input” ON.
・
Stopping (“Power” switch OFF): When the beeper becomes a sustained beep,
release the switch.
・
In Commercial Power Mode (“Power” switch ON): When the beeper changes from
intermittent beeps to a sustained beep, release the switch.
If you do not reset the battery life counter, a battery deterioration alarm may occur
faster than the expected battery life.
・
Stick the related Battery replacement date label on the Unit after writing the
battery replacement date.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......