9 References
9-1 Specifications
BU100RS
93
9
9 References
9-1 Specifications
Model
BU100RS
Method
Operation method
Full-time inverter supply method (Automatic Switching)
Cooling method
Forced air cooling
Input
Rated input voltage
100/110/115/120 VAC
Input voltage range
70±2 to 146±2 V AC (with less than 90% connection load)
80±2 to 146±2 V AC (with 90% or more connection load)
Frequency
Synchronous mode
50/60 Hz±5.5 Hz
Asynchronous mode
39 Hz to 71 Hz
Input Maximum current *1
13A
Phase
Single-phase, two-wire (grounded)
Input protection
Non Fuse Breaker (15A)
Input plug shape
3P (NEMA5-15P)
Output
Rated output capacity
1000 VA/800 W
Voltage
Commercial
operation
100V mode: 100VAC
±
2%, 110V mode: 110VAC
±
2%
115V mode: 115VAC
±
2%, 120V mode: 120VAC
±
2%
Backup operation
100V mode: 100VAC
±
2%, 110V mode: 110VAC
±
2%
115V mode: 115VAC
±
2%, 120V mode: 120VAC
±
2%
Frequency
Synchronous mode
Commercial operation: Synchronized with input frequency
Backup operation: 50/60 Hz
±
0.1 Hz
Frequency selection: Automatic selection when UPS start
Asynchronous mode
Commercial operation: 50/60 Hz
±
0.5%
Backup operation: 50/60 Hz
±
0.5%
Waveform
Commercial operation
Sine wave
Backup operation
Sine wave
Distortion rate
6% max. (Rectified load, at rated output)
3% max. (Resistance load, at rated output)
Phase
Single-phase, two-wire (grounded)
Output receptacle
NEMA 5-15R x 4 / Terminal block
Battery
Type
Sealed lead battery
Voltage / Capacity x Quantity
12 V / 9 Ah x 2
Backup time (25°C, initial characteristics)
5 min. or more (700W) / 4 min. or more (800W)
Charging time
8 hours
Battery life
Ambient temperature 25°C
Expected life: 5 years
Environ-
ment
Operating environment temperature/ humidity
0
°
C to 40
°
C, 25 to 85%RH with no condensation
Storage temperature
-15
°
C to 40
°
C, 10 to 90%RH with full charged and no condensation
Safety standard / RoHS directive compliance
UL1778 / RoHS compliant
Disturbance voltage /
Radiated interference field strength
VCCI Class A compliant
Internal power consumption (normal/maximum)
20W / 60W
Noise
50 dB
Dimensions (W x D x H) *4
438 mm x 378 mm x 85 mm (including the input cable cover)
Weight of unit
Approx. 13 kg
*1: Minimum input voltage 70V for 100V mode with 90% load
*2: Dimensions without input cable cover: 438 x 315 x 85
Note: About ECO mode, see p. 42.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......