2 Installation and connection
2-2 Connecting the equipment
BU100RS
33
2
2-2-2 Connecting a device to a terminal block
Caution
(for connection)
Connect only devices with rated voltage 100-120 VAC.
●
The rated output voltage of the product is 100-120 VAC.
●
Overvoltage may damage a connected device.
For other cautions when connecting the UPS, refer to “Caution (for installation and
connection)” shown in the “Safety precautions” of the beginning of this manual.
Caution
(for installation and connection)
For wiring, ensure that the output wiring capacity satisfies the
specifications for the load devices.
Make sure to properly match the AC output terminal. Connect to the AC
output terminal of the product with the AC input being cut off and the
power supply switch being turned "OFF". Be sure to attach the terminal
block cover.
●
Failure to do so may result in electric shock or ground fault.
●
Do not connect to the input side of the AC terminal block because connection has
already been made there.
Insert an emergency stop switch or externally-installed breaker between
the load devices and the product, and arrange it where it is easy to
operate.
■
Connection procedure
1.
Loosen the clamp on the side of the AC input cable, then remove the screws for the
terminal block cover and detach the terminal block cover.
Содержание BU100RS
Страница 96: ...9 References 9 2 Dimensions BU100RS 95 9 Vertical floor mounting bracket BAP100R 200 60 170 150 ...
Страница 97: ...9 References 9 2 Dimensions BU100RS 96 Rubber feet 21 358 40 40 3 240 25 25 ...
Страница 98: ...9 References 9 2 Dimensions BU100RS 97 9 Using Ear brackets 288 27 469 30 ...
Страница 100: ...9 References 9 4 China RoHS Information BU100RS 99 9 9 4 China RoHS Information ...
Страница 101: ......