1700 Series UPS  

 

Option Module Connection Guide 

 

IMPORTANT SAFETY INSTRUCTIONS 

 

SAVE THESE INSTRUCTIONS.

  

This sheet contains important instructions for Toshiba 1700 Series Transformer Modules.  

These instructions should be followed during the installation of the transformer module. 
 

 

The ambient temperature range in which this unit should be operated or stored is 32°F to 104 

°

F (0°C to 40 

°

C). 

 

This module should not be opened under any circumstances.  There are no user servicable parts inside.   For service 
contact your local Toshiba representative, or contact the Toshiba UPS marketing department toll-free at (800) 231-
1412. 

 

When adding transformer modules, be sure to use the proper model unit. 
 

 

CAUTION 

Misuse of this equipment could result in human injury and equipment damage.  In no event will 
Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that 
may result from the use of this equipment. 

 

Inspection/Installation 

After Unpacking: 
1)  Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all 

original packing materials for return to shipping agent.  Warranty will not apply to units damaged during shipment. 

2)  Check to see that the rated capacity and the model number specified on the nameplate conform to the order 

specifications. 

 

Installation Precautions 
This transformer module is intended for use with a Toshiba 1700 Series UPS.  Any electrical or mechanical 
modifications to this equipment, without prior written consent of Toshiba International Corporation will void all 
warranties and may void UL/CUL listing.  Unauthorized modifications also can result in personal injury, death, or 
destruction of the equipment.  
When installing this transformer module follow all installation instructions and precautions 
as listed in the 1700 Series user manual.
 

 
Specifications

 

UF1-IO- 

Model Number 

024-6AA 

024-6EE 

Capacity 

2400VA 

(1.68kW) 

2400VA 

(1.68kW)

 

Input voltage 

Single phase 

120VAC 

Single phase 

230VAC 

Input 
frequency 

45 to 65 Hz 

Input capacity 

2400VA 

2400VA 

In

p

u

Input power 
factor 

Approximately unity (0.95 to 1.0) 

Output 
voltage 

Single phase 

120VAC 

Single phase 

230VAC 

Output 
voltage 
regulation 

/- 3%, steady state 

Output 
frequency 

50/60 Hz (+/- 0.5% in free running 

mode, line sync range +/-1%) 

Rated load 
power factor 

0.7 

O

u

tp

u

Rated output 
current (rms) 

20A 

10A 

Figure 1 

Module Layout 