162
CompoNet Network Specifications
Section E-1
In Data Rate of 4
Mbps (No T-branching
allowed, *)
* Slave Units that are pre-connected with cables. do not support multidrop
connection. Therefore, they cannot be used at this data rate.
CompoNet Master Board
Trunk line
Terminating
Resistor
Sub-branch line
Repeater
Unit
Repeater
Unit
Repeater
Unit
Repeater
Unit
Repeater
Unit
Sub-trunk
line
Sub-trunk
line
Sub-trunk
line
Sub-trunk
line
Branch line
Branch line
Branch line
Branch line
Branch line
Branch line
Slave Unit
Slave Unit
Repeater Unit
Slave Unit
Branch line
Branch line
Trunk line length
Sub-trunk line length
Sub-branch
line length
Branch line length
Slave Unit
T-branch connection
Multidrop connection
Terminating Resistor
Sub-trunk
line
Sub-
trunk
line
Item
Round cable I or II
Flat Cable I or II
Length of a trunk line or a sub-
trunk line (Maximum length when
two Repeater Units are used)
30 m (90 m)
30 m (90 m)
Length of a branch line
No T-branch connection on the trunk line is
allowed.
Only multidrop connections are possible from
the trunk line and sub-trunk lines.
Total length of branch lines
Branching restriction
Number of connectable Slave and
Repeater Units altogether per
trunk line or sub-trunk line
32 32
Содержание 3G8F7-CRM21
Страница 4: ...iv...
Страница 10: ...x TABLE OF CONTENTS...
Страница 30: ...10 Specifications Section 1 7 1 7 3 Dimensions 3G8F7 CRM21 PCI unit mm 3G8F8 CRM21 CompactPCI unit mm...
Страница 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Страница 74: ...54 Board Hardware Error Notification Section 4 8...
Страница 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Страница 230: ...210 Wiring for Power Supply Section E 5...
Страница 234: ...214 Index...
Страница 236: ...216 Revision History...
Страница 237: ......