159
CompoNet Network Specifications
Section E-1
Flat Cable I (DCA4-4F10
Standard Flat Cable)
Types of Flat Cable I other than DCA4-4F10 can be used as long as they
conform to the CompoNet specifications. Ask the cable manufacturer for
information on which products are applicable to CompoNet.
Flat Cable II (DCA5-4F10
Sheathed Flat Cable)
Conductor
No.
Insulation
color
Application
Nominal
cross-
section
(mm
2
)
Allowable
current (A)
1
Red
BS + (positive side of
communications power
supply)
0.75
5 max.
2
White
BDH (signal high)
0.5
−
3
Blue
BDL (signal low)
0.5
−
4
Black
BS
−
(negative side of
communications power
supply)
0.75
5 max.
White: BDH Blue: BDL
Red: BS
+
Black: BS
−
Conductor
No.
Insulation
color
Application
Nominal
cross-
section
(mm
2
)
Allowable
current (A)
1
Red
BS + (positive side of
communications power
supply)
0.75
5 max.
2
White
BDH (signal high)
0.5
−
3
Blue
BDL (signal low)
0.5
−
4
Black
BS
−
(negative side of
communications power
supply)
0.75
5 max.
White: BDH Blue: BDL
Red: BS
+
Black: BS
−
Содержание 3G8F7-CRM21
Страница 4: ...iv...
Страница 10: ...x TABLE OF CONTENTS...
Страница 30: ...10 Specifications Section 1 7 1 7 3 Dimensions 3G8F7 CRM21 PCI unit mm 3G8F8 CRM21 CompactPCI unit mm...
Страница 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Страница 74: ...54 Board Hardware Error Notification Section 4 8...
Страница 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Страница 230: ...210 Wiring for Power Supply Section E 5...
Страница 234: ...214 Index...
Страница 236: ...216 Revision History...
Страница 237: ......