145
Command Specifications
Section B-4
Command
STOP_CYCLE
Purpose
Stop the communications cycles.
Code
0x1003
Argument
None
Set 0x0000.
Response code
Normal end: 0x0000
At an error:
Status change not allowed: 0x8101
Remarks
•
To resume the communications, the CompoNet Master Board must be reset.
•
These are the possible causes of having a situation in which no status
change is allowed.
•
The communications cycles have stopped.
Command
REQUEST_STATUS
Purpose
Issue a request to read the Detailed status group.
Code
0x2001
Argument
Reading status
1-WORD data,
items
Set the bits to read to 1 (ON) and the bits not to read to 0
(OFF).
Response code
Normal end: 0x0000
Remarks
•
The Detailed status in the shared memory that has been requested to read
is reflected at the time a normal end is the response.
Bit
Flag name
0
Duplication error flag
1
Registration error (Registered Slave not
participated) flag
2
Registration error (Non- registered Slave
participating) flag
3
Repeater configuration error
4
EO Slave Unit
5
Master status
6
Error counter
7
Network power state
8
Participating Slave Unit identity table
9
Repeater configuration information
10
Alarm information
11
Error log
12 to 13
Reserved area, Set 0 (OFF).
14
Registration table example
15
Reserved area, Set 0 (OFF).
Содержание 3G8F7-CRM21
Страница 4: ...iv...
Страница 10: ...x TABLE OF CONTENTS...
Страница 30: ...10 Specifications Section 1 7 1 7 3 Dimensions 3G8F7 CRM21 PCI unit mm 3G8F8 CRM21 CompactPCI unit mm...
Страница 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Страница 74: ...54 Board Hardware Error Notification Section 4 8...
Страница 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Страница 230: ...210 Wiring for Power Supply Section E 5...
Страница 234: ...214 Index...
Страница 236: ...216 Revision History...
Страница 237: ......