Capacitance and Dissipation Factor Measurement
The last measurement is C H. Figure 5-26 shows this connection diagram. The
measuring mode is GSTg-A+B. C HL and C HT are not measured, because they
are connected to GUARD.
The build-in relay matrix enables the described four different measurements
without any rewiring. This principle can be used not only for transformers, but
also for any system with partial capacitors inside.
Figure 5-26
Measurement of C H in GST-gA+B mode, C HL and C HT are
guarded
5.4
References
IN A
IN B
C
HL
C
HT
C
H
GSTg-A+B
C = C
H
[2.1]
Schering, H.: "Brücke für Verlustmessungen", Tätigkeitsbericht
der Physikalisch-Technischen Reichsanstalt, Braunschweig
1919
[2.2]
Hensler, Th., Kaufmann, R., Klapper, U., Krüger, M., Schreiner,
S.: "Portable testing device", US Patent 6608493, 2003
[2.3]
Krüger, M.: "Prüfung der dielektrischen Eigenschaften von
Isolierflüssigkeiten", ÖZE, No. 5, Vienna, May 1986
[2.4]
"IEEE Standard Test Code for Liquid-Immersed Distribution,
Power, and Regulating Transformers", IEEE Std C57.12.90-
1999
Содержание CP TD1
Страница 1: ...CP TD1 Reference Manual...
Страница 14: ...CP TD1 Reference Manual V 1 44 14...
Страница 20: ...CP TD1 Reference Manual V 1 44 20...
Страница 32: ...CP TD1 Reference Manual V 1 44 32...
Страница 38: ...CP TD1 Reference Manual V 1 44 38...
Страница 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Страница 114: ...CP TD1 Reference Manual V 1 44 114...
Страница 128: ...CP TD1 Reference Manual V 1 44 128...
Страница 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Страница 184: ...CP TD1 Reference Manual V 1 44 184...
Страница 186: ...CP TD1 Reference Manual V 1 44 186...