As shown in Figure 6-2, the three phases of the high-voltage (H), the low-voltage
(L) and the tertiary (T) windings are connected internally in y or delta. This way
only the sum of all three phases can be measured, the single phases can not be
measured separately. Figure 6-3 shows the simplified circuit diagram of the
three-phase transformer of Figure 6-2.
Figure 6-3
Three-phase transformer with winding capacitances
A
Phase A
B
Phase B
C
Phase C
H
High-Voltage
winding
C H
Cap. H to Ground
C H-L Cap. H to
L
L
Low-Voltage winding C L
Cap. L to Ground
C L-T Cap. L to T
T
Tertiary winding
C T
Cap. T to Ground
C H-T Cap. H to
T
H
High-Voltage
winding
C H
Cap. H to Ground
C H-L Cap. H to
L
L
Low-Voltage winding C L
Cap. L to Ground
C L-T Cap. L to T
Core
Tank
G
C
L-T
C
H-L
C
H
C
T
C
L
H
L
T
Содержание CP TD1
Страница 1: ...CP TD1 Reference Manual...
Страница 14: ...CP TD1 Reference Manual V 1 44 14...
Страница 20: ...CP TD1 Reference Manual V 1 44 20...
Страница 32: ...CP TD1 Reference Manual V 1 44 32...
Страница 38: ...CP TD1 Reference Manual V 1 44 38...
Страница 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Страница 114: ...CP TD1 Reference Manual V 1 44 114...
Страница 128: ...CP TD1 Reference Manual V 1 44 128...
Страница 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Страница 184: ...CP TD1 Reference Manual V 1 44 184...
Страница 186: ...CP TD1 Reference Manual V 1 44 186...