Influence of different parameters like water content,
temperature and aging on DF
Figure 5-10 shows the breakdown voltage and the DF in oil, dependent on the
water content [2.3]. With low water content, the breakdown voltage is very
sensitive; with higher water content, the DF is a good indicator.
Figure 5-10
Breakdown voltage and DF in oil, dependent on the water
content