147
Appendix
12.9.1
Introduction
Due to ever-increasing pressure to reduce costs, the power industry is forced to
keep old power facilities in operation as long as possible. In most European
countries, about one third of the transformers are older than 30 years.
Transformers, which are older than 50 years can still be found in service [1].
Figure 12-5
110/220 kV transformers in Germany
With the advancing age of transformers, a regular check of the operating
conditions becomes more and more important. The Dissolved Gas Analysis is a
proven and meaningful method such that if increased proportions of
hydrocarbon gases are found in the oil, the fault must be located as soon as
possible. This way, important preventative maintenance can be performed in
time to avoid an unexpected total failure (Figure 12-6) [2].
Existing 110kV / 220kV transformers in Germany
0
10
20
30
40
1 to 10
11 to 20
21 to 30
> 30
Age in years
P
ropo
rt
ion
in
%
110 kV transformers
220 kV transformers
Содержание CP TD1
Страница 1: ...CP TD1 Reference Manual...
Страница 14: ...CP TD1 Reference Manual V 1 44 14...
Страница 20: ...CP TD1 Reference Manual V 1 44 20...
Страница 32: ...CP TD1 Reference Manual V 1 44 32...
Страница 38: ...CP TD1 Reference Manual V 1 44 38...
Страница 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Страница 114: ...CP TD1 Reference Manual V 1 44 114...
Страница 128: ...CP TD1 Reference Manual V 1 44 128...
Страница 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Страница 184: ...CP TD1 Reference Manual V 1 44 184...
Страница 186: ...CP TD1 Reference Manual V 1 44 186...