CP TD1 Reference Manual V 1.44
104
7.8
Interpretation of Measurement Results
In the appendix typical DF values and limits are listed. Figures 7-11 and 7-12
show the aging of RBP, RIP and OIP bushings [4.5].
Figure 7-11
Aging of RBP, RIP and OIP bushings (change of capacitance)
10
8
6
4
2
0
10
8
6
4
2
0
10
8
6
4
2
0
0
5
10
15
20
25
30
35
40 years
C-change
in %
RBP
C-
ch
an
ge
in
%
OI
P
C-
ch
an
ge in % RIP