Capacitance and Dissipation Factor Measurement
39
5
Capacitance and Dissipation Factor
Measurement
Capacitance (C) and Dissipation Factor (DF) measurement is an established
and important insulation diagnosis method. It can detect:
• Insulation failures
• Aging of insulation
• Contamination of insulation liquids with particles
• Water in solid and liquid insulation
• Partial discharges
5.1
Theory
In an ideal capacitor without any dielectric losses, the insulation current is
exactly 90° leading according to the applied voltage. For a real insulation with
dielectric losses this angle is less than 90°. The angle
δ
= 90° -
ϕ
is called loss
angle. In a simplified diagram of the insulation, C
p
represents the loss-free
Содержание CP TD1