85
The CT Analyzer Test Cards
VA *
Cos
ϕ
Nominal burden of the CT, used to calculate the behavior of the CT at the
nominal burden.
Possible values: 0 to 300VA or soft keys
1.0VA
to
30VA
or
?
1
.
Depending on the burden and the selected test standard, the corresponding
cos
ϕ
is used (cos
ϕ
not editable by the user).
* This parameter is relevant for assessment. No automatic assessment is
available if the user did not enter data for this parameter prior to the test (see
page 82).
If the IEEE C57.13 standard is selected with the type "metering CT", the
CT Analyzer
offers some soft keys (e.g.
B-0.1
,
B-0.2
,
B-0.5
etc.) with
standard loads for the power. If these soft keys are used, the power is
calculated according to table 9 of IEEE C57.13. If the rated current is not 5A,
the resistance and inductance of the table is multiplied by the factor
If the IEEE C57.13 standard is selected with the type "protection CT" (class
C, K or T), the VA and Cos
ϕ
parameters are not accessible to the user. In
this case, the user has to enter the terminal voltage V
b
parameters and settings displayed for IEEE C57.13 protection CTs" on
page 98.
Burden
Cos
ϕ
"Burden" and "Cos
ϕ
" are used to define the operating burden connected to
the CT. These parameters are used to calculate the behavior of the CT at
the operating burden (connected burden) and the corresponding cos
ϕ
.
Possible values for "Burden": 0 to 300VA or soft keys
1.0VA
to
30VA
or
?
1
.
Possible values for "Cos
ϕ
": 0 to 1.
These parameters can also be changed after the test or in a loaded test
report in order to check the CT behavior at different burden values.
Special behavior depending on available test cards:
If the test contains a
Burden
card, a question mark is automatically entered
to the fields "Burden" and "cos
ϕ
" and entering the burden is not possible
until the test is finished. In this case, the value determined during the burden
test is automatically entered after burden measurement. If I
sn
is defined, the
burden is updated immediately after the burden test is finished. If I
sn
is not
defined (entry "?"), the burden is updated after the resistance test.
f
Rated frequency of the CT.
Possible values: Integer value between 16 and 400 Hz or soft keys
16.7Hz
,
50Hz
,
60Hz
or
400Hz
.
Default: Frequency defined in the default test settings.
Parameter
Description
α
5
I
rated
-------------
2
=
Содержание CT Analyzer
Страница 1: ...CT Analyzer CT SB2 User Manual...
Страница 3: ...CT Analyzer User Manual...
Страница 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Страница 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Страница 50: ...CT Analyzer User Manual 48...
Страница 60: ...CT Analyzer User Manual 58...
Страница 80: ...CT Analyzer User Manual 78...
Страница 162: ...CT Analyzer User Manual 160...
Страница 172: ...CT Analyzer User Manual 170...
Страница 188: ...CT Analyzer User Manual 186...
Страница 194: ...CT Analyzer User Manual 192...
Страница 195: ...CT SB2 User Manual...
Страница 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Страница 204: ...CT SB2 User Manual 10...
Страница 206: ...CT SB2 User Manual 12...
Страница 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Страница 212: ...CT SB2 User Manual 18...
Страница 226: ...CT SB2 User Manual 32...
Страница 242: ...CT SB2 User Manual 48...
Страница 248: ...CT SB2 User Manual 54...
Страница 250: ...CT SB2 User Manual 56...
Страница 252: ...CT SB2 User Manual 58...