CT Analyzer User Manual
108
6.6
Excitation Card
The
Excitation card
is only available if it is enabled in the
Select Cards
page
(Default Test Card Selection or
Select Cards
soft key in the
CT-Object
card).
The excitation test is used to trace the excitation curve of the current transformer
and to determine many CT-specific parameters (see test results below). The test
is done completely automatically up to a current of 15A
peak
.
CTs with closed cores can be tested up to a knee point voltage of 30kV. For CTs
with gapped cores the maximum test voltage and current are limited depending
on the maximum output power of the device. Typical maximum current and
voltage values for a TPZ core are 9A
rms
at 1200V
rms
.
The settings for the excitation test are specified in the
CT-Object
card. For a
better understanding of the test results, the most important settings from the
CT-Object
card are shown in the upper part of the
Excitation
card.
The test results displayed in the lower part of the
Excitation
card depend on the
standard selected in the
CT-Object
card. Using the soft keys, the user can
choose between different sets of results. If the
Results with Nom. Burden
soft
key is pressed, the page shows the results related to the nominal burden ("VA"
parameter in
CT-Object
card). If the
Results with Op. Burden
soft key is
pressed, the page shows the results related to the operating burden ("Burden"
parameter in
CT-Object
card).
Pressing the
Excit. Graph
soft key opens a page with the excitation graph (see
Pressing the
AL Error Graph
soft key opens a page with a graph showing the
maximum possible primary current (K * I
pn
) that can flow over a specific burden
without exceeding the accuracy limit (5% or 10%).
Figure 6-12
Excitation
card with values related to nominal burden
If the
CT Analyzer
displays an overload in the
Excitation
card, either the desired
knee point could not be reached or not all necessary measurement points could
be taken (e.g. in the knee point area, not enough points for a proper calculation
of the knee point could be measured).
Содержание CT Analyzer
Страница 1: ...CT Analyzer CT SB2 User Manual...
Страница 3: ...CT Analyzer User Manual...
Страница 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Страница 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Страница 50: ...CT Analyzer User Manual 48...
Страница 60: ...CT Analyzer User Manual 58...
Страница 80: ...CT Analyzer User Manual 78...
Страница 162: ...CT Analyzer User Manual 160...
Страница 172: ...CT Analyzer User Manual 170...
Страница 188: ...CT Analyzer User Manual 186...
Страница 194: ...CT Analyzer User Manual 192...
Страница 195: ...CT SB2 User Manual...
Страница 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Страница 204: ...CT SB2 User Manual 10...
Страница 206: ...CT SB2 User Manual 12...
Страница 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Страница 212: ...CT SB2 User Manual 18...
Страница 226: ...CT SB2 User Manual 32...
Страница 242: ...CT SB2 User Manual 48...
Страница 248: ...CT SB2 User Manual 54...
Страница 250: ...CT SB2 User Manual 56...
Страница 252: ...CT SB2 User Manual 58...