CT Analyzer User Manual
24
2.4
Connection for Usual Applications
2.4.1
Wiring for a CT Test
This section shows the basic wiring of the
CT Analyzer
for a CT test.
Observe the general safety rules in section 2.1 on page 21 and the hints and
instructions for improving the quality of the measurement results given in section
2.7 on page 42.
For a CT test, connect the
CT Analyzer
as shown in Figure 2-2:
1. Make sure that the primary side of the CT is connected to PE on one side and
open on the other side.
2. Disconnect the hot side of all secondary windings of the CT in order to
remove any load from the CT. Every kind of load remaining on the secondary
side of the CT during measurement leads to incorrect measurement results
or error messages.
3. Connect the black socket of
CT Analyzer
input "Prim" to the grounded side
of the CT’s primary circuit and the red socket of this input to the open
(ungrounded) side.
Warning:
Feeding test voltage to a tap of a
multi-ratio CT
can cause life-
threatening voltages on other taps with higher ratios. Do not touch these taps!
Caution:
The grounded terminal on the secondary side of the CT always has
to be connected to the black sockets of input "Sec" and the "Output" of the
CT Analyzer
. Connecting the red sockets of the
CT Analyzer
to PE can result
in incorrect measurement and/or cause an automatic abortion of the
measurement with an error message.
Caution:
If it is necessary to use clamps for the connection of the
measurement leads to the secondary side of the test object, always use the
4-wire connection technique as described in section 2.7.1 on page 42 in order
to avoid measurement errors.
Caution:
It is absolutely important to avoid coupling of interferences into the
primary circuit during measurement. Therefore, connect the side of the primary
circuit that is able to receive more interferences to PE (e.g. the side with the
longer line length). The ungrounded side should be the side that receives less
interferences (refer to Figure 2-2).
Содержание CT Analyzer
Страница 1: ...CT Analyzer CT SB2 User Manual...
Страница 3: ...CT Analyzer User Manual...
Страница 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Страница 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Страница 50: ...CT Analyzer User Manual 48...
Страница 60: ...CT Analyzer User Manual 58...
Страница 80: ...CT Analyzer User Manual 78...
Страница 162: ...CT Analyzer User Manual 160...
Страница 172: ...CT Analyzer User Manual 170...
Страница 188: ...CT Analyzer User Manual 186...
Страница 194: ...CT Analyzer User Manual 192...
Страница 195: ...CT SB2 User Manual...
Страница 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Страница 204: ...CT SB2 User Manual 10...
Страница 206: ...CT SB2 User Manual 12...
Страница 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Страница 212: ...CT SB2 User Manual 18...
Страница 226: ...CT SB2 User Manual 32...
Страница 242: ...CT SB2 User Manual 48...
Страница 248: ...CT SB2 User Manual 54...
Страница 250: ...CT SB2 User Manual 56...
Страница 252: ...CT SB2 User Manual 58...