26
921468007_09_010
«ZONE WITH DELAY». The zone will trigger an alarm event after an entrance delay. This selection is
used for the magnetic contacts that are used for the main entrance and also for the radar the will de-
tect the user before he reaches the panel to disarm it. For wireless PIR sensor and magnetic sensor,
the selection is forced from the device Dip-switch and it is validated only in the technician menu. If the
user selects anything else except for
“zone with delay” or “zone with no delay”, then the panel setting
is forced and the Dip-switch has no effect. Changing the Dip-switch of the device outside technician
menu has no effect. The user must enter technician menu, change the Dip-switch and press the tam-
per of the device, in order to validate the delay option.
«ZONE WITHOUT DELAY». The zone will trigger an immediate alarm. This selection is used for radar
detectors and magnetic contacts that are used in other areas. For the delay settings read the proce-
dure above in the paragraph
«ZONE WITH DELAY».
«PANIC». This zone will trigger an immediate alarm event, even though the panel is disarmed. It will
also produce a panic alarm message if a telephone dialer is installed. It can be used on zones that
have a panic button.
«FIRE». This zone will trigger an immediate alarm event even if the panel is disarmed. It will also pro-
duce a fire alarm message if a telephone dialer is installed. It can be used on zones that have smoke
and heat detectors.
«SILENT». The zone will trigger an immediate silent alarm event. It will activate the telephone dialler if
installed and not the sirens. It can be used in zones that have a panic button and the human that op-
erates it is being threatened by not using it.
«ZONE NEXT DELAY». When this option is activated, the system will arm after (EXIT TIME+EXTRA
EXIT TIME) time.
«SET SECTION». When this zone is activated it will arm the whole system or a section of it. It can be
used to arm the panel through some other system such as a BMS or fire alarm system. The zone must
be connected with a normally closed contact of the relay of the other system. If this setting is made by
a keyboard,
‘’YES’’ should be selected in zone bypass and forced arming selection.
«UNSET SECTION». When this zone is activated it will disarm the whole system or a section of it. It
can be used to disarm the panel when some other system such as a BMS or fire alarm system is also
disarmed. The zone must be connected with a normally closed contact of the relay of the other sys-
tem.
If this setting is made by a keyboard,
‘’YES’’ should be selected in zone bypass and forced arm-
ing selection.
«SET UNSET SECTION». When this zone is activated it will change the state of the panel or a section
of it from armed to disarmed and vice versa. It can be used to arm the panel through some other sys-
tem such as a BMS or fire alarm system. The zone must be connected with a normally closed contact
of the relay of the other system. If this setting is made by a keyboard,
‘’YES’’ should be selected in
zone bypass and forced arming selection.
«PG CONTROL». As far this particular zone is enabled, the selected output will also be activated. In
this option the technician must choose between P1, P2, P3 or RELAY.
«TAMPER». This zone will trigger an immediate alarm event, even if the panel is disarmed. It can be
used as a zone for connecting the TAMPER outputs of the external siren or the other devices.
«RADAR 2 PULSES». This is a special zone type is used for avoid false alarms. Only radars (PIR
sensors) must be connected to this zone. When the panel is armed it operates with the following way:
If the panel receives the first alarm signal from the specific zone, it waits for 5 minutes. If during this
interval, the panel receives a second signal, an immediate alarm is triggered. If during the 5 minute
interval a second signal is not received by the panel, then the first signal is considered to be a false
alarm and is discarded.