57
921468007_09_010
If, for example, the "Wireless Extension" option is selected at the same time with a "BS-458" panel,
which does not support this function, the panel will not contain wireless zones because this feature
does not exist on BS-458 panels.
Also, if "BS-458" panel is selected, it is up to the installer to choose whether the specific panel has a
GSM extension.
After selecting the panel type, the home screen appears, where the desired modifications can be
made.
Finally, we can save table properties to a file.
Panel's Firmware Update
In case the panel is to be upgraded, its settings are lost. If we want to prevent this, we have to follow
the following procedure:
1) Receive All Settings
2) Save (of all data in .oaf file)
3) Firmware Upgrade (Ctrl-F1)
The firmware of BS-468/A can be updated through the program BS-468. From the menu, press
"HELP"
"Firmware Update Ctrl-F1". In order to go on through the procedure, the user has to be
connected as "TECHNICIAN". The panel has to be connected to the PC through the USB port that is
present on the main panel board and NOT on the keypad BS-466/A.
The user is asked if he agrees with the upgrade. At this point, the version in which the table will be
upgraded is also mentioned. For the latest version of the board program, it is necessary to download
the latest version of the PC-468 program from the company's site.
During the next step the user will be asked to type the TECHNICIAN user password once again and
the upgrade procedure starts. A window box appears. If the message "Press any key to continue..."
comes out, then you have to press the "ENTER" key in the PC keyboard.
During upgrade procedure, the power supply to the panel and the connection to the PC should not be
interrupted.
When the procedure is finished, the user has to press "OK" at the dialogue box that appears and the
program shuts down automatically.
Continuing, it is essential that the USB has to be disconnected as well as the power supply and bat-
tery must stay unplugged for 30 seconds. After that time period connect the battery and power supply.
ATTENTION! For safety reasons, the user should not unplug the USB cable, while the PC
program is active. If, however, disconnection occurs, the panel for about 1 minute is pro-
grammed to stay in "TECHNICIAN" mode, to avoid data loss.