3.7
Mounting
The panel is provided as a package. The package contains the mounting screws and accessories and the instruction manuals.
Remove the panel from the package and locate the lock keys which can be found on the top side of the panel.
Mount the panel in an area that is visible and easily accessible by the personnel that are responsible for the fire safety of the
building. The panel is suitable for wall mounting in interior areas. Mounting the panel to the wall uses 3 points in the base of
the panel chassis.
3.7.1
Installing a loop to the panel
To properly install a loop to the panel adhere to the following guide lines:
1)
The maximum number of devices that can be connected to a loop is 150. In this case the connection cable must
be at least 1,5mm in diameter.
2)
Firstly we have to set the address of each device with care. The address setting is done using the micro-switches
on each device.
3)
Make a general installation plan that contains definitions for device information, addresses, cable lengths and
cross-section and any other useful information that we help to debug the system in the final stages of
commissioning.
4)
Before connecting the loop cables to the panel check the system for possible errors. These errors could be: short
circuits that can be found using a multi-meter, reverse polarity cables and finally cables that are not connected
properly or are disconnected.