Figure 5-15
Function configuration
To change the activation mode move the arrow to point to
«ACTIVATION MODE»
and press
«ENTER».
A window opens with
the following options :
ZONES (OR)
: The function is activated when any chosen zone is activated.
ZONES (AND)
: The function is activated when all chosen zones are activated.
Select the desired option using the
«UP»
and
«DOWN»
key and press
«ENTER»
to confirm the selection.
To change the selected zones move the arrow to point to
«ZONE SELECTION»
and press
«ENTER»
. A window will open with all
the zones. Move the cursor
«^»
under the zone that is required using the «LEFT» and «RIGHT» keys and select the zone by
pressing the «UP» key. This places the zone into the group. When this is done an asterisk is shown over the cursor.
While exiting press
«ENTER»
to save the changes. If
«ESC»
is pressed then no changes are stored.
Finally to store the changes we have made in the function configuration move the arrow to point to
«TO STORE CHANGES
PRESS ENTER»
and press the
«ENTER»
key.
5.4.5
Setup - Groups
If we select the group configuration option then a window will open that will permit us to select which group we want to
configure. The group number can be changed using the
«UP»
,«DOWN»
,
«PAGE UP»
and
«PAGE DOWN»
keys.