Date
9/7/2018
File
BSR-2114/MAR
Document Number
921211401_09_002
Page
18 από 74
18
3
Installation instructions
This section contains information regarding the connection of the panel with its peripherals, the programming of all the
functions and the elimination of the faults. It should be read carefully by all the installers who want to install and commission
a fire detection system. A good knowledge of the panel’s capabilities and its peripheral devices is an essential aid in designing
an operable installation.
3.1
General Description
The
BSR-2104/MAR and BSR-2114/MAR
panels are addressable fire detection panels with 2 or 4 loops and expansion
capabilities up-to 8 loops and 32,64 or 96 zones. Each loop can accept up-to 150 input units (sensors, call points) , output
units and line isolators.
The maximum number of fire detectors and manual call points connected to a panel must not exceed 512.
All units can be programmed to correspond to a specific zone without any device per zone limitations. Each point must have
its own individual address which is set using micro switches on each unit. The instruction manual of each unit shows in detail
the position of each micro switch that corresponds to each address.
The peripherals that can be connected to a loop of the panel are the following:
-
BSR-6055/A/MAR. Addressable smoke detector.
-
BSR-6057/A/MAR. Addressable smoke detector/heat detector.
-
BSR-6060/A/MAR. Addressable heat of rise detector.
-
BSR-5036/Α/MAR. Addressable call point.
-
BSR-8017/MAR. Addressable input/output unit with auxiliary relay.
-
BSR-5032/MAR. Addressable siren with beacon.
-
BSR-5032/WP/MAR. Waterproof Addressable siren with beacon.
-
BSR-7070/Α/MAR. Addressable line isolator. (Does not register as point in the panel and does not require an
address) .
-
BSR-7071/Α/MAR. Addressable line isolator. (Does not register as point in the panel and does not require an
address) .
On the siren outputs of the unit we can connect all the conventional sirens (BS-531
/MAR
, BS-531/WP
/MAR
).
All addressable detectors have a remote led output.
In order to minimize the errors during the installation and programming stages it is mandatory to have a general plot or
diagram. On the diagram we mark the address of each point, the name that it will be given (up to 32 characters) and that
zone that it will belong too.
The panel can be programmed and commissioned by using the built in keypad.
According to regulations, it is mandatory that during a loop short circuit, not more that 32 detectors will fail. To comply
to this, it is required that a line isolator is placed after every 32 detectors or points.
3.2
Safety
A device is not considered that it is being used correctly if the accompanying documents are not read prior to its use.
This product must be installed, commissioned and maintained by qualified technical personnel according to:
Regulations referring to installing electrical devices in buildings
Practice rules.
The statutes requirements.
The manufactures instructions.
- The unit operates with 220-240VΑC / 50-60Hz and is rated as a class1 device
(requires a grounding wire for safe operation).
- It must be installed and connected to the power line using its own safety fuse with a warning label
«Fire detection system –
Do not isolate»
.