These outputs can be used to signal fire alarm equipment such as diallers etc.
These outputs are according to EN 54-2.
These ouput can be used to operate in diffently to default setting, but then they will not fulfil the EN 54-2.
3.4.8
Fault routing connection
The panel has provision of Fault routing.
The Fault Alarm Routing terminal is the terminal ,-.
The output is monitored for open and short circuit fault condition.
Relay
+
-
Fault Routing
C
NC
NO
Activation
Normal
+VCC
Figure 3-15 Fault warning routing connection.
These outputs are according to EN 54-2.
These ouput can be used to operate in diffently to default setting, but then they will not fulfil the EN 54-2.
3.4.9
Various other connections
The panel also has the following available outputs:
Input/Output board
-
Extension +A , -A terminals
: These outputs are used for connecting external devices to the panel (i.e. external
relays, repeaters).
-
V_OUT terminal.
24V DC output voltage (up to 600mA) can be used to power devices that cannot be powered by the
loop (i.e. gas detectors or automatic door release electromagnetic latches).
-
FAULT terminal .
Open collector outputs. When there is a general fault this output is permanently activated (0V)
where as when there is a fault of the main processor the output is toggled on and off.
-
ALARM terminals .
Open collector outputs. When there is a general alarm the output is continuously activated (0V).
When there is an alarm in the operation of the main processor then the output is toggled ON and OFF.